background image

7

If suspending the air handler from the ceiling, assemble a support 

frame (

Figure 5

) using slotted iron channel and full threaded rod. 

Fasten the frame together with nuts, washers, and lockwashers. 

Secure the support frame to the rafters with lag bolts. The air 

handler can also be suspended using steel straps around each 

end of the unit. The straps should be attached to the air handler 

with sheet metal screws and to the rafters with bolts.

Horizontal Left Installations

1. Remove the coil access door.

2. Remove the plug from one of the threaded holes in the 

horizontal drain pan. Completely remove the webbing in the 

threaded holes of the horizontal drain pan. 

If the webbing 

is not removed, the condensate will not drain properly 

and ceiling damage may occur.

3. Insert the plug (from horizontal drain pan) into the open and 

unused drain hole in the drain pan at the bottom of the unit 

to block bypass air.

4. Remove the corresponding drain line knockout from the coil 

access door to allow access to the horizontal drain.

5. Replace the door and attach the drain line.

Horizontal Right Installations

1. Remove the coil access door. Unscrew the line-set tube 

close-off plate from the front left cabinet rail.

2. Slide the coil and drain pan assembly out of the unit.

3. Remove the sheet metal hairpin covers (if supplied) from the 

back of the coil and discard.

4. Place the horizontal drain pan on the opposite side of the coil. 

On units with 2 sets of knockouts, remove the other set of 

knockouts in the coil spacing plates and insert support rod.

5. Slide the coil and the horizontal drain pan assembly back into 

the unit. Re-attach the tube close off plate.

 

NOTE:

 For A-size cabinet applications, it may be preferrable 

to remove the blower assembly prior to installing the coil & 

drainpan. In this case follow instructions 1-4 as listed above 

but also remove the blower access door and blower assembly. 

The blower assembly is secured with two screws on either 

side near the front. With these removed the blower assembly 

can slide out of the front of the unit. Install the coil and drain 

pan as described in step 5 and then replace the blower 

assembly. Take care to ensure that the flanges on the sides 

of the blower assembly are captured by the pockets in the 

blower deck. It may be necessary to lift the blower assembly 

during insertion to allow the lower blower leg to clear the side 

of the drain pan. The blower will stop against the back of the 

blower deck. Replace the two screws and the blower access 

door and procede with steps 6-9.

6. Remove the plug from one of the threaded holes in the 

horizontal drain pan. Completely remove the webbing located 

in the threaded holes of the drain pan.

 IMPORTANT:

 If the 

webbing is not removed, the condensate will not drain properly 

and ceiling damage may occur.

7. Insert the plug (from horizontal drain pan) into the open and 

unused drain hole in the drain pan at the bottom of the unit 

to block bypass air.

8. Remove the corresponding drain line knockout from the coil 

access door to allow access to the horizontal drain.

9. Replace the door and attach the drain line.

Figure 4. Downflow Brackets

Rear

Bracket

Front

Joining

Bracket

Cased

Coil

Modular

Air Handler

NOTES:

•  In many applications when joined with a cased coil, the 

shorter horizontal drain pan extension which is included with 

the MB7 must be used. This is to avoid any interference with 

the extension included with the cased coil.

•  The air handler may or may not be shipped from the factory 

with all the parts required for horizontal left applications and 

horizontal right applications. If your unit does not have parts 

for a horizontal application, a kit may be available.

•  In horizontal right applications where the air handler is in a 

humid location in an unconditioned space, it is recomended 

to install a condensate shield kit over the control board.

Figure 5. Unit Horizontally Suspended

Threaded 

Rod

Lag
Bolt

Nuts (x2)

Washer 

and 

Lockwasher

Nuts (x2)

Summary of Contents for MB7EM 3-PHASE Series

Page 1: ...ll Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury d...

Page 2: ...ion Check 10 Running the Blower Continuously 10 System Cooling 10 System Heating 10 Turning the Blower Off 10 Blower Configurations 10 Selecting Minimum Electric Heat Airflow 10 Determining Nominal Sy...

Page 3: ...s otherwise noted in these instructions only factory authorized kits or accessories may be used with this product The installer should become familiar with the units wiring diagram before making any e...

Page 4: ...gh the bottom of the unit the joint between the air handler and the return air plenum must be air tight Return air and circulating air ducts must not be connected to any other heat producing device su...

Page 5: ...nwithanoutervaporbarrier Consult your Distributor for the recommended type and thickness of insulation for your area as required by local codes Condensate Drainage CAUTION The air handler must be leve...

Page 6: ...ill connect with the supply air duct 4 Carefullyplacethecasedcoilontopofthemodularairhandler NOTE Make sure the units are flush in the front and on the sides with a step fit in the back and that there...

Page 7: ...lowerassembly The blower assembly is secured with two screws on either side near the front With these removed the blower assembly can slide out of the front of the unit Install the coil and drain pan...

Page 8: ...on delay a 15 second blower off delay in electric heat mode and a 40 second ELECTRICAL CONNECTIONS WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could res...

Page 9: ...lug of the heater kit 2 Connectthelinevoltageleadstothecircuitbreakerorterminal block provided 3 Connect the heater kit plug with the mating receptacle on the air handler control board If a heater kit...

Page 10: ...se there are so many different ways to set up the air handler it is important to read and follow these directions carefully MB7EM MB7VM air handlers use high efficiency circulating air motors that com...

Page 11: ...NG ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result in dangerous operation serious...

Page 12: ...DIMENSION E A 12 3 4 24 3 4 14 1 4 12 3 4 3 4 B 12 3 4 24 3 4 17 1 2 16 2 3 8 C 18 1 4 27 1 2 21 19 1 2 1 3 8 B A 12 7 8 E 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1...

Page 13: ...or Mount Kit Blower Motor Blower Wheel Blower Housing Transformer Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Rear Bracket Front Joining Bracket Motor Control Board Control Board F...

Page 14: ...1778 1727 1684 1613 1542 1 1 0 1 1935 1932 1884 1840 1795 1727 1659 1614 0 0 1 1 2070 2023 2009 1953 1906 1851 1800 1724 1 0 1 1 2138 2079 2063 2003 1951 1889 1830 1765 0 1 1 1 2161 2111 2091 2058 201...

Page 15: ...100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400...

Page 16: ...UIT CIRCUIT A CIRCUIT B CIRCUIT C SINGLE CIRCUIT MB7VM 240 VAC 50 60 Hz Single Phase A 1 200 CFM 4 5 4 5 15 15 B 1 600 CFM 4 5 4 5 15 15 C 2 000 CFM 6 3 6 3 15 15 208 VAC 50 60 Hz Single Phase A 1 200...

Page 17: ...on after 15 seconds delay OFF Heat stages off instantly Blower off after 15 second delay W1 Y Y2 AUX HEAT ON 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on i...

Page 18: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Page 19: ...HEATER P1 L 2 HUM EAC P2 3A Fuse P3 EXPANSION PORT Figure 11 Two Stage Control Board All Models Figure 10 Low Voltage Wiring For Twinning Y R C Outdoor Unit A H 1 C R Y G W W G Y R Thermostat 1 A H 2...

Page 20: ...DHUM W1 THERMOSTAT EXPANSION PORT COOL HEAT FAN SPEED 1 2 3 4 5 6 7 8 OFF ON CONNECTION TERMINAL TO TWIN FURNACES GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN...

Page 21: ...RAM 3 Transformer may have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the internal wiring is replaced use only 105 C copper wire of the same gauge 3 Le transfo...

Page 22: ...ns d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Page 23: ...23...

Page 24: ...duct according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when instal...

Reviews: