WARNING
Failure to provide floor protection can result
in a home fire and personal injury.
A
B
C
D
E
U.S.
35.75 in.
8 in.
36.5 in.
16 in.
2 in.
908 mm 203 mm 927 mm
406 mm 51 mm
CAN
35.75 in.
8 in
43.75 in.
18 in.
2 in.
908 mm 203 mm 1111 mm 457 mm 51 mm
Floor Protection
Any floor that is not composed of concrete poured on earth requires protection from sparks and embers. The
Kube is approved for installation using one of the following forms of hearth protection:
Any UL, ULC, or Warnock Hersey Listed Type 1 hearth board.
Any noncombustible material.
In the U.S. floor protection must extend continuously forward from the door opening at least 16 in. and 8 in.
from the sides of the door opening. Protection must also extend 2 in. under the chimney connector. This will
result in a minimum floor protector 35 3/4” wide x 36 1/2” deep. See Fig 3.
In Canada, floor protection must extend continuously 18” from the front of the stove and 8 in. (460 mm) from
the sides and rear. It must also extend 2 in. (51 mm) to both sides under a horizontal chimney connector sec-
tion. This results in a floor protector 35 3/4 in. x 43 3/4 in. (85 cm x 111 cm). See Fig. 3.
Fig. 3