REDUCING VENT SIZE: TRANSITIONING FROM 3" TO 2"
VENT PIPE MUST ALWAYS TAKE PLACE IN A VERTICAL
POSITION TO PREVENT CONDENSATE BLOCKAGE.
3 inch pipe
2 inch pipe
(A field supplied PVC reducer bushing must be used.)
Chapter 4. – Installation
Vent Pipe Installation
Tightening
•
You can select the size of vent pipe(2" or 3") according to the installation conditions.
• Push the pipe into the unit flue until it touches the bottom.
• Tighten the band clamps using a screwdriver.
• Finally, make sure that both pipes(exhaust & air intake) are securely fixed.
Vent Termination
Vent Screen Installation
• Install vent screen (Only 3
"
vent screens are included as accessories), see the below figure for appropriate
configuration.
• After connecting vent/air inlet terminal, it is required to install screen for the terminal to prevent incoming of
debris and animals, which might cause damage to the unit.
(2
"
vent screen (1/4
"
mesh) must be purchased for 2
"
venting installation)
Allowable Schedule 40 Vent Length (PVC, CPVC)
* The termination elbow must be included in the total number of elbows.
Maximum Vent Length
The unit can be adjusted to accommodate longer vent runs; refer to the below table to find the maximum vent
length based on the number of elbows.
3" vent screen (1/4" mesh)
Pipe diameter
3
"
(75mm)
2
"
(50mm)
No. of Elbows
Max Equivalent Vent Length*
6
70
´
N/A
5
75
´
N/A
4
80
´
18
´
3
85
´
26
´
2
90
´
34
´
1
95
´
42
´
0
100
´
50
´
• 5 feet (1.5M) for each additional
3-inch 90-degree elbow
• 2.5 feet (0.75M) for each additional
3-inch 45-degree elbow
• 8 feet (2.4M) for each additional
2-inch 90-degree elbow
• 4 feet (1.2M) for each additional
2-inch 45-degree elbow
Reducer bushing