Chapter 5. – Installation Check
WARNING
Allowing the water heater to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat
exchanger as needed by the installation location could result in water heater failure, property damage, personal injury,
or death. Such product failures ARE NOT covered under warranty.
In unusually dirty or dusty conditions, care must be taken to keep water heater cabinet door in place at all times. Failure
to do so VOIDS WARRANTY!
CAUTION
The water heater requires minimal periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions,
periodic vacuuming of the cover to maintain visibility of the display and indicators is recommended.
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating
safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of
the water heater. Installer must also inform the owner that the lack of proper care and maintenance of the water heater may result in
a hazardous condition.
INSPECTION ACTIVITIES
DATE LAST COMPLETED
Piping
1st YEAR 2nd YEAR 3rd YEAR 4th YEAR
Near water heater piping
Check water heater and system piping for any sign of leakage. Leaking pipes
could cause property damage. Make sure all piping is properly supported. Flush
tankless heat exchanger annually (more in hard water conditions). See User’s
Information manual for instructions.
Vent
Check condition of all vent pipes and joints. Ensure all vent piping is properly
supported. Check for obstructions exhaust and intake termination points.
Gas
Check Gas piping, test for leaks and signs of aging. Make sure all pipes are
properly supported.
SYSTEM
Visual
Do a full visual inspection of all system components.
Functional
Test all functions of the system (Heat, Safeties)
ELECTRICAL
Connections
Check wire connections. Make sure they are tight.
Switch and Plug
Verify ON/OFF switch and convenience plug are both functional
CONDENSATE
Condensate Trap
Clean debris from the condensate trap. Fill with clean water.
Neutralizer
Check condensate neutralizer. Replace if necessary.
Condensate hose
Disconnect condensate hose. Clean out dirt and re-install. (NOTE: Verify the
flow of condensate, making sure that the hose is properly connected during final
inspection.)
GAS
Pressure
Measure incoming gas pressure (NG : 3.5" to 10.5" W.C.) (LP : 8.0" to 14" W.C.)
Check gas pipe for leaks Check piping for leaks. Verify that all are properly supported.
COMBUSTION
CO/CO2 Levels
Check CO and CO2 levels in Exhaust. Record at high and low fire.
Maintenance Report
MAINTENANCE REPORT