background image

28

Figure 23. Outdoor cooling unit

connection

3. 

Measure the time (in seconds) required for 
the gas meter to complete one revolution.

4. 

Convert the time per revolution to cubic feet 
of gas per hour using Table 11.

5.  Multiply the gas fl ow rate in cubic feet per 

hour by the heating value of the gas in Btu 
per cubic foot to obtain the fi ring rate in Btu 
per hour.  Example:

 

•  Time for 1 revolution of a gas meter with 

a 1 cubic  foot dial = 40 seconds.

 

•  From Table 14 read 90 cubic feet per 

hour of gas.

 

•  Heating value of the gas (obtained from 

gas   supplier) = 1040 Btu per cubic 
foot.

 

•  Firing rate = 1040 x 90 = 93,600 Btuh.

6. 

Adjustments to the fi ring rate can be made 
by adjusting the gas manifold pressure. 
See the High Altitude Application  section 
for additional information of fi ring rate at 
elevations above 2000 ft.

The manifold pressure for low and high inputs 
must be set to the appropriate value for instal-
lation (see Table 1).  Refer to either Table 6 for 
natural gas or Table 7 for LP/propane gas to 

verify the manifold pressure setting required for 
your particular installation. To adjust the manifold 
pressure, remove the regulator cap and turn the 
adjusting screw clockwise to increase pressure 
or counterclockwise to reduce pressure. Note: 
Check both low and high inputs to the Table 1.  
Replace the regulator cap after adjustments 
are complete.

 CAUTION:

Do not re-drill  the burner orifi ces.  If 
the orifi ce size must be changed, use 
only new orifi ces

.

 WARNING:

To avoid electric shock, personal injury, 
or death, disconnect the electric power 
before performing any maintenance

.

Selecting The  Cooling  Airfl ow Rate

The thermostat controller communicates with the 
outdoor unit to determine the proper airfl ow. The 
system will operate automatically at the optimum 

THRU CORE RING

TO L.V. BARRIER

THRU CORE

RING

OUTDOOR UNIT

INVERTER

OUTDOOR UNIT

CONTACTOR

R

C

W2 W

H

TWIN

DX

+

DX-

24 VAC

INTERFACE
BOARD

YELLOW

GND
DX-
DX+

CN11

T1

T1

L1

L1

BLACK

BLACK

BLA

CK

BLACK

O

.D

. UNIT

RED

WHITE

GREEN

RED

WHITE

GREEN

GND

Y

Summary of Contents for TE Series 95

Page 1: ...or maintenance can cause injury or property damage Refer to this manual for assistance For additional information consult a qualified installer service agency or the gas supplier FOR YOUR SAFETY Do n...

Page 2: ...ort 15 Location of Outdoor Terminations 18 Horizontal Venting 18 Vertical Venting 19 Vent Freezing Protection 19 Concentric Vent Termination 20 Drainage of Condensate From Furnace 20 Gas Supply and Pi...

Page 3: ...s A B Combustion Air Vent 3 See Fig 15 for sizes 1 1 2 x 3 1 2 Dia Opening for Gas Connection 3 4 3 4 3 4 22 1 2 Exhaust Vent Combustion Air Inlet 1 1 2 x 3 1 2 Dia Opening for Gas Connection C 2 PVC...

Page 4: ...these instructions 10 The furnace is not to be used for temporary heating of buildings or structures under construction INSTALLATION REQUIREMENTS Requirements and Codes Thisfurnacemustbeinstalledinacc...

Page 5: ...oratory as recognized under 527 CMR 3 A Product approved vent terminal must be used and if applicable a Product approved air intake must be used In stallation shall be in strict compliance with the ma...

Page 6: ...use of unauthorized parts may void the manufacturer s product warranty coverage The 90 upflow furnace can be installed hori zontally in an attic basement crawl space or alcove This furnace can be inst...

Page 7: ...Tee Soft Tubing Looped to Provide a Drain Trap 3 to 2 Reducer Optional Drainage Port is Downward Reducer Bushing Alternative for Horizontal Vent Pressure Switch Pressure Switch Condensate Vinyl Cap Fi...

Page 8: ...be connected to any other heat producing device such as a fireplace insert stove etc CIRCULATING AIR SUPPLY Plenums and air ducts must be installed in ac cordance with the Standard for the Installatio...

Page 9: ...taminated with various household chemicals which can cause severe corrosion in the furnace combus tion system NOTE If the furnace is operated without ad equate air for combustion and ventilation it ma...

Page 10: ...y involves installation in a small room All such installations must have specific provisions for introduction of combustion and ventilation air Codes require that two openings be provided for this one...

Page 11: ...oved for use with these condensing furnaces Table 3 Vent Table table provided in this section applies to the total of vent and combustion air piping for either type of installation These condensing fu...

Page 12: ...Air Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ducts must extend above attic insulation Air Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ventilation Louve...

Page 13: ...ilding 4 Follow the lighting instructions Place the appliance being inspected in operation Adjust thermostat so appliance shall operate continuously 5 Turn on clothes dryers and any other appliance no...

Page 14: ...ion requires breakable connec tions in the piping Note that a maximum of two couplings per pipe are allowed Upflow Furnaces Combustion Air Pipe Exhaust Vent Cabinet 5 Support System on Vertical Rise B...

Page 15: ...longradiuselbow Therefore forour example we have three additional long radius elbowsforwhichwemustaddtoourpiping Each long radius elbow is equivalent to 2 5 feet so we must add 7 5 feet to our vent le...

Page 16: ...000 Btuh 3 kW and 100 00 Btuh 30 kW 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW C Clearance to permanently closed window D Vert...

Page 17: ...other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3 kW and 100 00 Btuh 30 kW 36 inches 91 cm for appliances 100 00 Btuh 30 kW 4 feet 1 2 m belo...

Page 18: ...eCanadianFuelGasCodetakes precedence over these instructions Specifi cally allminimumdistancerequirementswith respecttoterminationoftheventpipinglisted below items 1 through 8 The following list is a...

Page 19: ...or pulled through the wall 4 Insure the combustion air inlet pipe for a 2 pipeinstallation hasa90degreetermination elbow as shown in Figures 16 and 17 Note A combustion air intake must be provided wi...

Page 20: ...4 Route the tubing out of the hole located 8 inches up from the bottom furnace The condensate should drain from the plastic collector box location A in Figure 18 as droplets or a small stream If you...

Page 21: ...J Drain Tube Clamp Loosen For Step 1 Retighten for Step 3 Route to floor drain OR Route to condensate pump Keep downward slope Collector Box A Rotate counter clockwise Step 2 Upflow Models the Nationa...

Page 22: ...jury or death Figure 19 Typical Gas Service Connection MANIFOLD PRESSURE ADJUSTMENT Manifold pressures for low and high stages are independently adjustable Adjustment tap locations on the valve are sh...

Page 23: ...500 440 400 370 350 1 1 2 1600 1100 890 760 670 610 560 530 For a Natural Gas Sea Level Heating Value of 800 to 899 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 24: ...nace to replace the pressure switch or to utilize LP propane gas must be made by qualified service personnel using factory authorized or approved parts High altitudeapplicationswiththisfurnacecanbefie...

Page 25: ...for the control system to operate correctly Verify that the incoming neutrallineisconnectedtothewhitewireand the incoming hot line is connected to the blackwireinthejunctionbox Thesefurnaces will not...

Page 26: ...ler The thermostat controller must not be installed on an outside wall or any other location where itsoperationmaybeadverselyaffected Adverse effects include radiant loading from fireplaces sunlight o...

Page 27: ...rocedures After all of the above checks have been made 1 Close the disconnect s to provide line volt age to the furnace 2 Setthermostatcontrollerusingtheinstaller s instructions also refer to Table 1...

Page 28: ...alue for instal lation see Table 1 Refer to either Table 6 for natural gas or Table 7 for LP propane gas to verify the manifold pressure setting required for yourparticularinstallation Toadjustthemani...

Page 29: ...f the supply air limit switch make sure that the blower door is in place and that there is power to the furnace Completely block the return airflow to the furnace by install ing a close off plate in p...

Page 30: ...e vent pressure switch reacts to blockage in the vent or combus tion air piping Supply Air Limit Switch The supply air limit switch prevents the air temperature leaving the furnace from exceeding the...

Page 31: ...N TEMP SENSOR SUCTION PRESS SENSOR GREEN BLACK WHITE RED RED EXV 6 WIRE CABLE CABLE WHITE GREEN GREEN BLACK 3 PIN PLUG 6 PIN PLUG WHITE BLACK FURNACE BOARD GREEN RED RED YELLOW GRAY RED YELLOW RED BLU...

Page 32: ...the bearings is required for the life of the motor Condensate Drain Assembly Be sure the condensate lines are free and open i e avoid kinking hoses Also make sure all hose clamps are tight to avoid dr...

Page 33: ...lower Door Switch 10 Vent Safety Switch 11 Low Voltage Transformer 12 Supply Air Limit Switch 3 4 12 18 14 7 9 11 23 5 6 22 10 16 13 15 21 8 17 20 2 1 13 Circulating Air Blower Assembly 14 Induced Dra...

Page 34: ...eignitionfeaturewhich varies the warm up period as follows If igni tion is successful the warm up is reduced by 3 seconds on each subsequent call for heat until ignition failure occurs Upon igni tion...

Page 35: ...ng 1 Is the thermostat operating properly 2 Are the blower compartment door s in place 3 Is the furnace disconnect closed 4 Has the circuit breaker tripped or the control board fuse burned open 5 Is t...

Page 36: ...k tested _______ Gas Line Pressure _____________________ in water column with furnace operating Manifold Pressure ______________________ in water column with furnace operating Is there adequate fresh...

Reviews: