background image

6

HEAT PUMP INSTALLATION

General Information
Split system heat pumps are designed only for outdoor 
rooftop or ground level installations. This unit has been 
tested for capacity and efficiency in accordance with 
AHRI Standards and will provide many years of safe 
and dependable comfort, providing it is properly installed 
and maintained. Abuse, improper use, and/or improper 
maintenance can shorten the life of the appliance and 
create unsafe hazards.

To achieve optimum performance and minimize equipment 
failure, it is recommended that periodic maintenance be 
performed on this unit. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools.

Before You Install this Unit

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 
It is recommended that the area to be conditioned be 
completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 
and provided with circuit protection in accordance with 
local building codes. If there is any question concerning 
the power supply, contact the local power company.

  The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to 
the indoor unit's installation instructions for installation 
details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 
prior to installing the equipment at the job site. Verify 
coil fins are straight. If necessary, comb fins to remove 
flattened or bent fins. Claims for damage (apparent or 
concealed) should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

Locating the Heat Pump

• 

Survey the job site to determine the best location for 
mounting the outdoor unit. See Figure 4 (page 11) for 
unit dimensions.

•  Overhead  obstructions  (Figure  2),  poorly  ventilated 

areas, and areas subject to accumulation of debris 
should be avoided.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 
performance. See Figure 2 for minimum clearances to 
obstructions.

• 

Consideration should be given to availability of electric 
power, service access, noise, and shade.

Packaging Removal
NOTE:  
To prevent damage to the tubing connections, 
carefully remove the carton and user’s manual from the 
equipment. Discard the shipping carton.

Ground Level
Ground level installations must be located according to 
local building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown 

in Figure 2.

•  A suitable mounting pad must be provided and separate 

from the building foundation. The pad must be level 
and strong enough to support the weight of the unit. 
The slab height must be a minimum of 2” (5 cm) above 
grade and with adequate drainage. See Figure 2.

Roof Mount

• 

The method of mounting should be designed so that it 
does not overload roof structures or transmit noise to 
the interior of the structure. The roof must be structurally 
capable of handling the weight of the unit.

• 

Full perimeter support is required under the unit. 
Support must be made of weather resistant materials 
and installed prior to unit installation.

•  The support must be built to raise the unit 6" above 

the roof.

24" for 

Service Access

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE:

 Units require full perimeter clearances. Installer must maintain

18” between two units or 12” between single unit and structure.

6” from Building

or Structure

12" or 18”

See Note

Figure 2. Clearance Requirements

2” Mounting Pad

48”

Summary of Contents for T5BD Series

Page 1: ...eliminate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalco...

Page 2: ...nits 18 Refrigerant Charging Tables Heating Mode 19 Table 10 T5BD 018K 1 5 Ton Units 19 Table 11 T5BD 024KA 2 Ton Units 19 Table 12 T5BD 030KA 2 5 Ton Units 20 Table 13 T5BD 036K 3 Ton Units 20 Table...

Page 3: ...system mode to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to ma...

Page 4: ...e aluminum fins Check and remove any obstructions such as twigs sticks etc TROUBLESHOOTING If the unit fails to operate check the following The thermostat is properly set See Cooling Operation for air...

Page 5: ...erant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individu...

Page 6: ...ility of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit See Figur...

Page 7: ...be in compliance with all applicable local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and groun...

Page 8: ...marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided wit...

Page 9: ...oom temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify t...

Page 10: ...he required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged Heat Pump MAINT...

Page 11: ...4 060K 43 30 3 4 30 3 4 D W H DO NOT OBSTRUCT TOP OF UNIT Allow adequate clearance for airflow reffrigerant Charging Charts Figure 5 Charging Chart for 1 5 Ton Units 125 150 175 200 225 250 275 300 32...

Page 12: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units T5BD 030KA Charging Chart 150 175 200 225 250 275 300 325...

Page 13: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units T5BD 042K Charging Chart 150 175 200 225 250 275 300 325...

Page 14: ...g Add refrigerant when below curve Remove refrigerant when above curve T5BD 048K Charging Chart Figure 11 Charging Chart for 5 Ton Units 150 170 190 210 230 250 270 290 310 330 350 75 80 85 90 95 100...

Page 15: ...Liq Press Dis Temp Liq Press Dis Temp 73 140 135 75 143 140 155 137 77 145 146 157 143 170 140 79 147 150 160 148 172 145 185 142 81 151 153 162 152 175 150 187 147 200 144 83 166 155 177 154 189 151...

Page 16: ...ss Dis Temp Liq Press Dis Temp 71 148 144 73 150 149 164 147 75 152 155 166 152 179 149 77 155 158 168 157 181 154 195 152 79 159 161 171 161 183 159 197 156 210 154 81 174 164 187 163 199 161 212 158...

Page 17: ...ss Dis Temp Liq Press Dis Temp 69 132 130 71 134 136 149 135 73 136 141 151 140 166 140 75 137 149 153 145 168 145 183 145 77 140 152 154 152 170 150 185 149 200 149 79 158 155 172 155 188 154 203 153...

Page 18: ...7 84 222 178 235 176 248 174 260 171 86 238 180 252 178 265 176 88 255 182 268 180 90 271 185 92 Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design...

Page 19: ...ress Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 12 120 107 21 135 119 29 150 131 37 165 142 46 169 158 56 184 177 66...

Page 20: ...ss Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 13 116 120 22 136 125 31 156 130 40 176 136 49 183 151 59 201 175 68 21...

Page 21: ...ess Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 23 129 118 27 140 124 31 151 130 35 162 136 44 173 149 58 206 168 72 2...

Page 22: ...159 139 31 182 143 39 206 147 48 230 158 58 257 175 68 283 193 16 142 133 24 165 137 32 187 141 40 209 145 49 237 155 59 264 171 69 290 187 17 149 131 25 171 135 33 192 139 41 213 143 50 244 152 60 27...

Page 23: ...avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre Single Phase OPTIONAL HARD START KIT Start Capacitor 2 5 Sta...

Page 24: ...8 1 4 1 4 1 4 1 4 1 4 Fan Blade Dia Blades 24 3 SCFM 2370 2370 3000 3000 3000 4000 4000 Compressor Data RLA 8 3 10 8 13 4 15 3 19 2 19 8 25 3 LRA 40 3 56 68 87 112 105 146 Refrigerant suction line Le...

Reviews: