background image

3

ABOUT THE HEAT PUMP

Your heat pump is a unique, all weather comfort-control 
appliance that will heat and cool your home year round 
and provide energy saving comfort. It’s an unknown fact 
that heat is always in the air, even when the outside 
temperature is below freezing. The heat pump uses this 
basic law of physics to provide energy saving heat during 
the winter months. For example, If the outdoor temperature 
is 47° F (8° C), your heat pump can deliver approximately 
3.5 units of heat energy per each unit of electrical energy 
used, as compared to a maximum of only 1 unit of heat 
energy produced with conventional heating systems.

In colder temperatures, the heat pump performs like an air 
conditioner run in reverse. Available heat energy outside 
the home is absorbed by the refrigerant and exhausted 
inside the home. This efficient process means you only 
pay for “moving” the heat from the outdoors to the indoor 
area. You do not pay to generate the heat, as is the case 
with more traditional furnace designs.

During summer, the heat pump reverses the flow of the 
heat-absorbing refrigerant to become an energy-efficient, 
central air conditioner. Excess heat energy inside the 
home is absorbed by the refrigerant and exhausted 
outside the home.

IMPORTANT SAFETY INFORMATION

Safety markings are used frequently throughout this 
manual to designate a degree or level of seriousness and 
should not be ignored. WARNING indicates a potentially 
hazardous situation that if not avoided, could result in 
personal injury or death. CAUTION indicates a potentially 
hazardous situation that if not avoided, may result in minor 
or moderate injury or property damage.

USER INFORMATION

OPERATING INSTRUCTIONS

Please refer to the thermostat manufacturer’s User manual 
for detailed programming instructions.

Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO 

and change the fan mode to AUTO. See Figure 1

2. Set the temperature selector to the desired temperature 

level. The outdoor fan, compressor, and blower motor will 
all cycle on and off to maintain the indoor temperature 
at the desired cooling level.

NOTE: If the temperature level is re-adjusted, or the 
system mode is reset, the fan and compressor in the 
outdoor unit may not start immediately. A protective 
timer circuit holds the compressor and the outdoor fan 
off for approximately 5 minutes following a previous 
operation or the interruption of the main electrical 
power.

Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO 

and change the fan mode to AUTO. See Figure 1.

2. Set the temperature selector to the desired temperature 

level. The compressor, outdoor fan, and blower motor 
will cycle on and off to maintain the indoor temperature 
at the desired heating level.

NOTE: If the temperature level is re-adjusted, or the 
system mode is reset, the fan and compressor in the 
outdoor unit may not start immediately. A protective 
timer circuit holds the compressor and the outdoor fan 
off for approximately 5 minutes following a previous 
operation or the interruption of the main electrical 
power.

Emergency Heat
Some thermostats may include a system mode called EM 
HT or AUX HT, etc. This is a back-up heating mode that 
should only be used if a problem is suspected. With the 
mode set to EM HT, etc., the compressor and outdoor fan 
will be locked off and supplemental heat (electric resistance 
heating) will be used as a source of heat. Sustained use 
of electric resistance heat in place of the heat pump will 
result in an increase in electric utility costs.

Defrost Operation
During cold weather heating operation, the outdoor unit 
will develop a coating of snow and ice on the heat transfer 
coil. This is normal and the unit will defrost itself. This unit 
monitors ambient and coil temperatures to regulate the 
defrost function accordingly.

Figure 1. Digital Thermostat

Fan

Mode

Temperature

Selector

System

Mode

Summary of Contents for T5BD Series

Page 1: ...eliminate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalco...

Page 2: ...nits 18 Refrigerant Charging Tables Heating Mode 19 Table 10 T5BD 018K 1 5 Ton Units 19 Table 11 T5BD 024KA 2 Ton Units 19 Table 12 T5BD 030KA 2 5 Ton Units 20 Table 13 T5BD 036K 3 Ton Units 20 Table...

Page 3: ...system mode to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to ma...

Page 4: ...e aluminum fins Check and remove any obstructions such as twigs sticks etc TROUBLESHOOTING If the unit fails to operate check the following The thermostat is properly set See Cooling Operation for air...

Page 5: ...erant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individu...

Page 6: ...ility of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine the best location for mounting the outdoor unit See Figur...

Page 7: ...be in compliance with all applicable local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and groun...

Page 8: ...marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided wit...

Page 9: ...oom temperature and verify the outdoor unit and indoor blower energize 2 Verify blower wheel is spinning in direction indicated by arrow Feel the air being circulated by the indoor blower and verify t...

Page 10: ...he required liquid refrigerant pressure determined in Step 3 there is too little charge in the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged Heat Pump MAINT...

Page 11: ...4 060K 43 30 3 4 30 3 4 D W H DO NOT OBSTRUCT TOP OF UNIT Allow adequate clearance for airflow reffrigerant Charging Charts Figure 5 Charging Chart for 1 5 Ton Units 125 150 175 200 225 250 275 300 32...

Page 12: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units T5BD 030KA Charging Chart 150 175 200 225 250 275 300 325...

Page 13: ...perature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units T5BD 042K Charging Chart 150 175 200 225 250 275 300 325...

Page 14: ...g Add refrigerant when below curve Remove refrigerant when above curve T5BD 048K Charging Chart Figure 11 Charging Chart for 5 Ton Units 150 170 190 210 230 250 270 290 310 330 350 75 80 85 90 95 100...

Page 15: ...Liq Press Dis Temp Liq Press Dis Temp 73 140 135 75 143 140 155 137 77 145 146 157 143 170 140 79 147 150 160 148 172 145 185 142 81 151 153 162 152 175 150 187 147 200 144 83 166 155 177 154 189 151...

Page 16: ...ss Dis Temp Liq Press Dis Temp 71 148 144 73 150 149 164 147 75 152 155 166 152 179 149 77 155 158 168 157 181 154 195 152 79 159 161 171 161 183 159 197 156 210 154 81 174 164 187 163 199 161 212 158...

Page 17: ...ss Dis Temp Liq Press Dis Temp 69 132 130 71 134 136 149 135 73 136 141 151 140 166 140 75 137 149 153 145 168 145 183 145 77 140 152 154 152 170 150 185 149 200 149 79 158 155 172 155 188 154 203 153...

Page 18: ...7 84 222 178 235 176 248 174 260 171 86 238 180 252 178 265 176 88 255 182 268 180 90 271 185 92 Shaded boxes indicate flooded conditions Rated design values The suction pressure will vary from design...

Page 19: ...ress Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 12 120 107 21 135 119 29 150 131 37 165 142 46 169 158 56 184 177 66...

Page 20: ...ss Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 13 116 120 22 136 125 31 156 130 40 176 136 49 183 151 59 201 175 68 21...

Page 21: ...ess Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp Suc Press Liquid Press Disch Temp 23 129 118 27 140 124 31 151 130 35 162 136 44 173 149 58 206 168 72 2...

Page 22: ...159 139 31 182 143 39 206 147 48 230 158 58 257 175 68 283 193 16 142 133 24 165 137 32 187 141 40 209 145 49 237 155 59 264 171 69 290 187 17 149 131 25 171 135 33 192 139 41 213 143 50 244 152 60 27...

Page 23: ...avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 volt a la terre Single Phase OPTIONAL HARD START KIT Start Capacitor 2 5 Sta...

Page 24: ...8 1 4 1 4 1 4 1 4 1 4 Fan Blade Dia Blades 24 3 SCFM 2370 2370 3000 3000 3000 4000 4000 Compressor Data RLA 8 3 10 8 13 4 15 3 19 2 19 8 25 3 LRA 40 3 56 68 87 112 105 146 Refrigerant suction line Le...

Reviews: