Table 9. Charging Table for T5BD-060K Series (5 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
66
143
146
68
145
152
159
149
70
147
157
161
154
175
152
72
148
164
163
159
178
157
192
155
74
152
167
165
165
180
162
194
159
208
157
76
169
168
182
167
196
164
210
161
224
159
78
185
170
198
168
212
166
226
164
240
161
80
202
172
215
170
228
168
242
165
256
163
82
205
175
218
174
232
172
244
169
258
167
84
222
178
235
176
248
174
260
171
86
238
180
252
178
265
176
88
255
182
268
180
90
271
185
92
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air flow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode
at ambient above 70°F.
REFRIGERANT CHARGING TABLES - COOLING MODE