17
Table 7. Charging Table for T5BD-042K Series (3.5 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
71
144
150
73
146
155
159
152
75
148
161
161
157
175
153
77
152
163
164
162
177
158
191
154
79
155
165
167
164
179
163
193
159
206
156
81
171
167
183
166
195
164
208
160
222
157
83
186
169
198
167
210
165
224
162
237
159
85
202
171
214
169
226
166
239
163
253
160
87
205
174
217
172
229
170
241
167
255
164
89
221
176
233
174
245
171
257
168
91
236
178
248
175
260
172
93
252
180
264
177
95
267
181
97
Table 8. Charging Table for T5BD-048K Series (4 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
69
132
130
71
134
136
149
135
73
136
141
151
140
166
140
75
137
149
153
145
168
145
183
145
77
140
152
154
152
170
150
185
149
200
149
79
158
155
172
155
188
154
203
153
218
153
81
176
158
190
158
205
158
220
157
235
157
83
193
162
207
162
222
162
237
161
252
161
85
197
166
211
166
225
166
239
165
254
165
87
214
170
229
170
243
170
256
169
89
232
174
246
174
260
174
91
250
178
264
178
93
267
183
95
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air flow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode
at ambient above 70°F.
REFRIGERANT CHARGING TABLES - COOLING MODE