17
T4BE-060KA SERIES
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70
75
80
85
90
95
100
105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
121
244
135
123
245
135
267
141
125
246
135
268
141
290
147
127
247
136
269
142
291
147
313
154
129
248
136
270
142
292
148
314
154
336
160
131
271
142
293
148
315
154
337
160
359
166
133
295
148
317
154
338
160
360
166
382
172
135
318
154
340
160
362
166
383
172
405
178
137
319
154
341
160
363
166
385
172
406
178
139
342
160
364
166
386
172
408
178
141
365
166
387
172
409
178
143
388
172
410
178
145
411
178
147
Table 11. Charging Table for 5 Ton Models
(Restrictor Matches)
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry
bulb, or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode, suction pressure will be lower than design value if indoor air flow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in cooling mode
at ambient above 70°F.