6 E2 Service Manual

Sequencer (Figure 2)
In general all sequencers operate the same way. In
some applications one sequencer may be sufficient
(10 and 12 kw models)  in other applications. One two
or more sequencers may be required.

Important: Sequencers should never be mixed.  If
different brands of sequencer are used and their timing
may be  different.

Testing Sequencer
1. Shut off the power supply to the furnace, there

could be two circuits. Be sure both "A" and "B"
circuits are de-energized.

a.

Remove all wires from the sequencer (making
note of wire color and terminal location). The
bi-metal heater portion of the sequencer will be
unmarked and at the bottom, closest to the
mounting plate. The switching portion will be
marked M1 through M8 depending on the
number of switches.  Refer to unit wiring
diagram.

b.

With an ohmmeter, test for continuity across
the bi-metal heater terminals. There should be
70 to 90 ohms of  resistance. If the meter reads
no continuity, the bi-metal heater is open and
must be replaced. The OHMS value should be
70 to 90 across the bi-metal.

Figure 2. Sequencer

c.

With an ohmeter check all switches in the
sequencer. They are labled M1-M2, M3-
M4...refer to Figure 2. All of the switches should
be open and have no continuity.

2. With all power on to furnace, and thermostat

contacts  closed:  using a voltmeter (set scale for
220 vac.)  On contact terminals of sequencer,
check each set of terminals of sequencer, check
each set individually. If you read voltage, contacts
are open. If you do not read voltage, contacts are
closed.  Allow a maximum time (110 seconds) for
heater to close contacts. If any of the contacts
remain open after three minutes the sequencer is
defective and should be replaced.

Indoor Coil
(optional)

Coil Air Filters
(used with indoor coil)

Furnace Air Filter
(NOT used with indoor coil
and coil air filters)

Data Label

Control Panel Cover
(right)

Control Panel Cover (left)

Circuit Breakers

A/C or H/P Relay Box  (optional)

Blower

Blower Selector Switch
(next to blower)

Summary of Contents for E2EB 010H

Page 1: ...E2 Series Electric Furnaces Service Manual ...

Page 2: ......

Page 3: ...Model Identification Code 4 Serial Number Identification Code 4 Selecting Blower Speeds 11 Blower Performance 12 Changing Blower Speeds 11 Service Diagrams 21 4 7 Wire Relay Box for H P E2EB 020 and 023 Units 23 2 Wire Relay Box for A C E2EH 020 and 023 Units 21 4 7 Wire Relay Box for H P E2EH 020 and 023 Units 22 Thermostat Sequence of Operation 12 Wiring Diagrams 13 E2EB 010 17 E2EB 012 18 E2EB ...

Page 4: ...tratedatlistedvoltage Foroutputsatvoltagesotherthan240V multiplyBtuhratingbythefollowingfactors x0 92 230V x0 84 220V x0 75 208V 2 Height is 56 with return air grille installed 58 with coil cabinet and 72 with coil cabinet and upflow stand 3 The factory installed blower for the EH models can be replaced with a multi speed blower allowing the units to accept up to 4 or 5 tons of air conditioning or...

Page 5: ...1 element and the blowermotor Astheheatercontinuestobuildupheat the bi metal closes the remaining circuits to other elements until all elements are on The off cycle is reverse of the on cycle the blower and no 1 element are first on and the last to be de energized Table 2 Optional Air Conditioning and Heat Pump Equipment Item Number See Fig 1 Description 1 4 Speed Blower 4 Ton See Notes 1 5 5 Ton ...

Page 6: ...be 70 to 90 ohms of resistance If the meter reads no continuity the bi metal heater is open and must be replaced The OHMS value should be 70 to 90 across the bi metal Figure 2 Sequencer c With an ohmeter check all switches in the sequencer They are labled M1 M2 M3 M4 refertoFigure2 Alloftheswitchesshould be open and have no continuity 2 With all power on to furnace and thermostat contacts closed u...

Page 7: ...e replaced Caution Heating elements must always be replaced byanidenticalkWreplacement Substitutionbyhigher kW s or elements of a different design may result in unsafe operation of the furnace Lower kW rated elements will reduce output and may result in unsatisfactory operation of the appliance Refer to element rating labels and furnace wiring diagrams Refer to unit wiring diagram section for wiri...

Page 8: ...metal disc to open a set of normally closed contacts The limit device is a safety which can be compared to a fuse or a breaker in a electrical circuit The function of the limit switch is to open the electrical circuit to the heating elements if over heating should occur This could be caused by air circulator failure dirty filters lackofreturnair restrictedducts etc Alllimitswitches used are of the...

Page 9: ...eiscontinuity the motor is grounded and should be replaced 4 Using the ohmmeter check the resistance across the motor leads See diagrams below Note the higher the speed the lower the resistance of the motor winding Figure 11 Blower Figure 9 Fan Switch Shematic Figure 12 Motor Schematic Checking the Air Circulator Selector Switch Tochecktheaircirculatorswitchshutofallpowertothe furnace Remove wires...

Page 10: ...onnecting Supply Service Wires 1 Remove right hand control panel when viewing in downflow position 2 Locate power supply hole plugs in side of unit and in bottom of unit Remove appropriate plug s or knockoutopeningapplicabletorecommendedwire size s 3 Install listed cable connector s in opening s If metal sheathedconduitisusedforincomingpower line s provideanapprovedmetalclamponconduit and secure i...

Page 11: ...yorpropertydamage make certain that the motor leads cannot come into contact with non insulated metal components of the unit See Table 4 for the lowest speed approved for the heating output of the unit Since the blower leads connect to the controlbox blowerspeedselectionisaccomplishedthrough use of the proper color coded blower lead located inside the controlbox Thespeed s setbythefactorymaybediff...

Page 12: ...nd set ventilate switch to AUTO Cooling system and air circulator blower should turn on 3 Check air temperature at supply duct registers 4 Move temperature setting lever until left hand cooling contacts open Cooling system and air circulator blower should turn off 5 Replace thermostat cover For Continuous Air Circulation and Ventilation NOTE ForCM65 seefurnaceowner smanualonindepen dent blower ope...

Page 13: ...13 E2 Service Manual Figure 15 E2EH 010 Wiring Diagram ...

Page 14: ...14 E2 Service Manual Figure 16 E2EH 012 Wiring Diagram ...

Page 15: ...15 E2 Service Manual Figure 17 E2EH 015 017 Wiring Diagram ...

Page 16: ...16 E2 Service Manual Figure 18 E2EH 020 023 Wiring Diagram ...

Page 17: ...17 E2 Service Manual Figure 19 E2EB 010 Wiring Diagrams ...

Page 18: ...18 E2 Service Manual Figure 20 E2EB 012 Wiring Diagram ...

Page 19: ...19 E2 Service Manual Figure 21 E2EB 015 017 Wiring Diagram ...

Page 20: ...20 E2 Service Manual Figure 22 E2EB 020 023 Wiring Diagram ...

Page 21: ...21 E2 Service Manual Figure 23 Two Wire Relay Box for A C E2EH 020 and 023 Units ...

Page 22: ...22 E2 Service Manual Figure 24 4 7 Wire Relay Box for H P E2EH 020 and 023 Units ...

Page 23: ...23 E2 Service Manual Figure 25 4 7 Wire Relay Box for H P E2EB 020 and 023 Units Part 1 ...

Page 24: ...24 E2 Service Manual Figure 26 4 7 Wire Relay Box for H P E2EB 020 and 023 Units Part 2 ...

Page 25: ...____________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ ___________________________________________...

Page 26: ...______________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _________________________________...

Page 27: ......

Page 28: ...St Louis MO 359A 1097 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 10 97 R R ...

Reviews: