Table 3. *SK - 80% AFUE, Single Stage, Downfl ow Gas Furnaces

DOWNFLOW GAS FURNACES

Model

Number

Heating

Input

(Btuh)

Motor

Speed

External Static Pressure (Inches Water Column)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

SK054(†)-23A

54,000

High*

1,375

29

1,340

30

1,300

31

1,270

31

1,225

33

1,175

34

1,115

36

1,035

39

Med-High

1,155

35

1,130

35

1,110

36

1,085

37

1,055

38

1,015

39

975

41

910

44

Med-Low**

790

51

775

52

765

52

750

53

730

55

700

57

665

60

610

66

Low

650

62

640

63

630

63

610

66

590

68

565

71

530

75

480

83

SK072(†)-24B

72,000

High*

1,610

33

1,590

34

1,575

34

1,560

34

1,540

35

1,495

36

1,460

37

1,415

38

Med-High

1,295

41

1,275

42

1,260

42

1,250

43

1,220

44

1,195

45

1,170

46

1,120

48

Med-Low**

1,155

46

1,135

47

1,115

48

1,095

49

1,065

50

1,040

51

1,015

53

980

54

Low

910

59

885

60

860

62

835

64

810

66

785

68

765

70

735

73

SK090(†)-24B

90,000

High*

1,675

40

1,655

40

1,640

41

1,620

41

1,590

42

1,560

43

1,520

44

1,475

45

Med-High

1,330

50

1,315

51

1,300

51

1,280

52

1,255

53

1,230

54

1,200

56

1,150

58

Med-Low**

1,180

56

1,165

57

1,150

58

1,135

59

1,115

60

1,090

61

1,060

63

1,010

66

Low

940

71

925

72

900

74

880

76

850

78

825

81

795

84

760

88

SK108(†)-35C

108,000

High*

2,395

33

2,335

34

2,285

35

2,230

36

2,200

36

2,140

37

2,080

38

2,000

40

Med-High

2,190

37

2,135

37

2,115

38

2,080

38

2,030

39

1,975

41

1,915

42

1,810

44

Med-Low**

1,785

45

1,770

45

1,740

46

1,725

46

1,685

47

1,645

49

1,615

50

1,565

51

Low

1,145

70

1,110

72

1,070

75

1,035

77

1,000

80

950

84

905

88

835

96

SK126(†)-45D

126,000

High*

2,445

38

2,395

39

2,385

39

2,330

40

2,275

41

2,225

42

2,130

44

2,015

46

Med-High

2,195

43

2,170

43

2,140

44

2,120

44

2,090

45

2,030

46

1,975

47

1,855

50

Med-Low**

1,795

52

1,780

52

1,770

53

1,760

53

1,725

54

1,690

55

1,655

56

1,610

58

Low

1,480

63

1,475

63

1,450

64

1,440

65

1,440

65

1,415

66

1,405

66

1,375

68

Notes

(†) Can be C or N

1. Temperature rises in the table are approximate. Actual temperature rises may vary.

* Factory Set Cooling Speed

2. Temperature rises shaded gray are for reference only. These conditions are not recommended.

** Factory Set Heating Speed

Summary of Contents for 045C-23ASA

Page 1: ...future reference GAS FURNACES Single Stage High Efficiency Furnaces Installation Instructions SA Upflow Horizontal Model SK Downflow Model 80 AFUE DO NOT DESTROY KEEP IN A SAFE PLACE FOR FUTURE REFERE...

Page 2: ...n Air Inlet 9 Bottom Return Air Inlet 9 Horizontal Installation 9 Bottom Panel Removal 10 Downflow Installation 10 Installation on a Concrete Slab 10 VENTING REQUIREMENTS 12 Category I Venting 12 Hori...

Page 3: ...naces 24 Figure 16 Downflow Furnaces 25 Airflow Data 26 Table 2 Upflow Horizontal Gas Furnaces 26 Table 3 Downflow Gas Furnaces 28 Electrical Information 29 Table 4 Wire length and Voltage Specs 29 Ta...

Page 4: ...ting outside the space containing the furnace This furnace may be used for temporary heating of buildings or structures under construction See the guidelines listed on page 5 Agas firedfurnaceforinsta...

Page 5: ...equires redundant inspections Serial numbers for furnaces used during construction must be submitted in writing fax and email also acceptable This information will be used to track the long term affec...

Page 6: ...ance from the front of the unit is 36 inches The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements COMBUSTION AIR REQUIREMENTS Gen...

Page 7: ...ppliance input The openings shall exchange directly or by ducts with the outdoor spaces crawl or attic that freely exchange with the outdoors Figure 3 Figure 3 Combustion Air Drawn from a Crawl Space...

Page 8: ...sq In 6 inches 140 000 35 sq In 7 inches 160 000 40 sq In 8 inches Furnace 12 Max Water Heater Vent or Chimney NOTES Each opening must be at least 100 sq in or 1 sq in per 1 000 Btuh of total input ra...

Page 9: ...nstalled horizontally in an attic basement crawl space or alcove Figure 6 It can also be suspended from a ceiling in a basement or utility room in either a right to left airflow or left to right airfl...

Page 10: ...built cased air conditioning coil However the plenum attached to the coil casing must be installed so that its surfaces are at least 1 from combustible construction Installation on a concrete slab 1 C...

Page 11: ...en the space in which the appliance s connected to the venting system are located and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dryers and any appliance not connected to...

Page 12: ...ventingsystemwillneed to be modified to comply with NFGC or local codes The venting system should be designed to have the minimum number of elbows or turns All horizontal runs shall slope upwards from...

Page 13: ...uding carbon monoxide poisoning that could result in personal injury or death All return ductwork must be secured to the furnace with sheet metal screws For installations in confined spaces all return...

Page 14: ...work may be connected to the left side right side or bottom The bottom panel Figure 15 page 24 must be installed for left or right return air NOTE Do not use the back of the furnace for return air Sid...

Page 15: ...o avoid unwanted noise and or damage to the furnace A typical gas service hookup is shown in Figure 11 Leak Check WARNING FIRE OR EXPLOSION HAZARD Never test for gas leaks with an open flame Check all...

Page 16: ...ecessaryforhigh altitude installation may only be accomplished with factory supplied orifices Do not attempt to drill out orifices in the field Improperly drilled orifices may cause fire explosion car...

Page 17: ...tor for the proper upgrade motor kit IMPORTANTNOTE Settheheatanticipatoraccording to the instructions supplied by the thermostat manufacturer To determine the heat anticipator setting 1 Add the curren...

Page 18: ...s on the terminal strip of the circuit board Verify the gas line service pressure does not exceed 10 0 inches of W C and is not less than 4 5 inches W C for natural gas For LP gas the line service pre...

Page 19: ...er to avoid false readings 2 Adjust all registers and duct dampers to the desired positionandrunthefurnacefor10to15minutesbefore taking any temperature readings The temperature rise is the difference...

Page 20: ...ir Limit Switch Note A properly functioning limit switch should turn off the gas valve when the return is blocked time depends on how well the return air is blocked The circulating air and combustion...

Page 21: ...that they were removed 12 Follow the lighting instructions found on the furnace door to return the furnace to operation Verify proper operation after servicing Cleaning Of Flue Passages If the flue p...

Page 22: ...of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death Check the vent pipe and or ch...

Page 23: ...Right Side 0 In Vent 1 In Back 0 In Top 1 In Front 4 In These are the listed clearances to combustible materials Allow 24 in minimum clearance for servicing Recommended clearance is 36 in The furnace...

Page 24: ...r N Dimensions shown in Inches Figure 15 SA 80 High Efficiency Upflow Horizontal Furnaces D 23 A 23 28 34 15 1 25 1 X 3 HOLE FOR GAS C 19 B 23 22 21 22 29 22 25 1 X 3 X 45 HOLE FOR GAS 4 KNOCKOUTS BOT...

Page 25: ...B FRONT BRACE 7 RIGHT SIDE LEFT SIDE BOTTOM VIEW FLANGES TOP VIEW 19 ACCEPTS 4 TYPE B VENT PIPE Figure 16 SK 80 High Efficiency Downflow Furnaces SK Model s Dimension A Dimension B Dimension C Dimensi...

Page 26: ...685 32 1 645 32 1 590 34 1 550 34 1 485 36 1 415 38 Med High 1 400 38 1 360 39 1 340 40 1 310 41 1 275 42 1 245 43 1 190 45 1 125 47 Med Low 1 235 43 1 215 44 1 180 45 1 155 46 1 130 47 1 100 48 1 060...

Page 27: ...65 1 175 68 SA108 35C Side Return 108 000 High 2 295 35 2 235 36 2 180 37 2 110 38 2 050 39 1 975 41 1 900 42 1 810 44 Med High 2 130 38 2 075 39 2 035 39 1 970 41 1 915 42 1 845 43 1 765 45 1 675 48...

Page 28: ...60 43 1 520 44 1 475 45 Med High 1 330 50 1 315 51 1 300 51 1 280 52 1 255 53 1 230 54 1 200 56 1 150 58 Med Low 1 180 56 1 165 57 1 150 58 1 135 59 1 115 60 1 090 61 1 060 63 1 010 66 Low 940 71 925...

Page 29: ...103 9 0 14 15 126 45D 126 000 24 115 60 1 127 103 15 2 12 30 NOTES can be C or N Time delay fuses or HACR type circuit breakers are required Thermostat Wire Gauge Recommended Thermostat Wire Length 2...

Page 30: ...K BLACK BLACK BLUE BLUE BLUE BLUE BLUE ORANGE BLUE GREEN BLUE BLACK BLACK WHITE BLACK WHITE WD 710731 C FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE For 80 and 90 Single Stage Furnaces SINGLE STAGE TH...

Page 31: ...176 353 48 75 375 750 104 35 173 346 50 72 360 720 106 34 170 340 52 69 346 692 108 33 167 333 54 67 333 667 110 33 164 327 56 64 321 643 112 32 161 321 58 62 310 621 114 32 158 316 60 60 300 600 116...

Page 32: ...HIGH HIGH Table 9 Natural Gas Heating Values Table 8 High Altitude Deration Chart for Propane Gas PROPANE GAS ALTITUDE ABOVE SEA LEVEL INPUT BTU 45 000 54 000 72 000 90 000 108 000 126 000 0 to 1 999...

Page 33: ...LD PRESSURE 9 000 to 9 999 FT 51 49 49 49 49 49 ORIFICE SIZE 2 6 2 8 2 8 2 8 2 8 2 8 MANIFOLD PRESSURE Table 11 High Altitude Deration Chart for Natural Gas Low Heating Value NATURAL GAS LOW HEATING V...

Page 34: ...34...

Page 35: ...OW ML MH HIGH EAC L1 XFMR HUM 24V L1A 5 NEUTRALS 2 6 3 4 1 7 8 9 5 2 6 3 4 1 FAN 8 4 7 3 11 1 9 10 13 12 2 5 6 ITEM COMPONENT NAME 1 Blower Assembly 2 Blower Door Switch 3 Burner Assembly 4 Combustion...

Page 36: ...esh air supply for combustion and ventilation YES NO Installation Altitude ____________________ FT Deration Percentage ___________________ Furnace Input _______________________ Btuh Supply Air Tempera...

Reviews: