Minimum distances to be observed
To prevent the water vapour, that is emitting from the steam distributors,
from condensing on downstream system components, a minimum distance
to the steam distributor must be observed (depends on the humidification
distance “B
n
”).
0.5 x B
N
50 mm
after expansion
0.5 x B
N
1 x B
N
before bend
1 x B
N
before/after constriction
before branch
before diffuser
before control sensor
1 x B
N
5 x B
N