15
E15 Program fault
Function:
indicates that the steam generator is blocked via the function
“Countdown”.
Procedure:
Error E15 may be reset only if the correct unlock code is
entered. If the unlock code gets lost the CPU board must be replaced or
newly programmed.
Behaviour on activation:
No Warning
Error
Display
-
E15: Program Fault
LED display:
-
Red
Fault-Remote:
-
Error Relay
Error-History:
-
E15
System:
-
Unit blocked
Time delay:
-
According to parameter Running Time
Reset:
-
automatic reset
E18 Temperature measuring instable
Function:
indicates that the drop in temperature in the steam bath cabin
is too high.
Procedure:
In order to detect a manipulation on the temperature sensor
the temperature curve of the temperature sensor is monitored during steam
bath operation.
If the temperature decreases by cooling the temperature sensor (e.g. by
the use of a cool rag) within a certain time “Time Range” by more than the
set temperature value, the steam generator is blocked.
The temperature monitoring is activate only during steam bath operation
and if the door of the steam bath cabin is closed.
Behaviour on activation:
No Warning
Error
Display
-
E18: Temperat.Instab.
LED display:
-
Red
Fault-Remote:
-
Error Relay
Error-History:
-
E18
System:
-
Unit blocked
Time delay:
-
-
Reset:
-
Automatic reset after blocking time has
elapsed