Settings in the engineering level
2.1
Launching the Engineering level
Select the engineering settings menu:
Path:
Main menu > User > Password entry: 1055 > Engineering
Press the
< >
and
< >
keys in order to select the individual settings in the engineering level. Detailed
information on the different settings are found in the following chapters.
2.2
Setting the intensity levels for the fragrance pumps
Select “
Fragrance
” in the engineering menu, then press the
<Set>
key. Select the intensity level (levels
1 to 5) whose values you would like to modify, then press the
<Set>
key.
Set the desired interval time in minutes and the pulse duration in seconds for the selected intensity level.
Setting range
interv
al time:
2...20 minutes
Setting range pulse duration:
2...10 seconds
Factory setting:
Level 1 = interval time: 10 minutes, pulse duration: 2 seconds
Level 2 = interval time: 8 minutes, pulse duration: 3 seconds
Level 3 = interval time: 6 minutes, pulse duration: 3 seconds
Level 4 = interval time: 4 minutes, pulse duration: 4 seconds
Level 5 = interval time: 3 minutes, pulse duration: 5 seconds
Note: the fragrance pump is active only, if the main contactor of the steam generator is activated and
the system is in steam bath operation.
Engineering Code
105
5
Enter Number
Confirm with Set
Esc
Set
FactoryReset:Set
Instab.Temp.:Set
Stop Mode :Switch
Min.Request :25/20%
Engineering
Max.op.hr SC:5000h
Drain Cool :On
GFCI :Set
Fragrance :Set
Overcurrent :Float
Esc
Set
Level 1
Impulse :2s
Interval :10min
Esc
Set
Level 1
Impulse :2s
Interval :10min
Esc
Set
Fragrance
Level 2 :Set
Level 3 :Set
Level 4 :Set
Level 1 :Set
Level 5 :Set
Esc
Set
Interval
10 min
10 min
Esc
Set
Impulse
2 s
2 s
Esc
Set
Engineering
Max.op.hr SC:5000h
Drain Cool :On
GFCI :Set
Fragrance :Set
Overcurrent :Float
Esc
Set
Main Menu
Light-2 :Off
User :Set
Engineering :Set
Fragrance :Set
Diagnostic :Set
Esc
Set
Menu
AT4D 65kg/h 400V3
Steam Bath :Standby
Temperature :34°C
Setpoint :48°C
2011-08-31 12:00:00
Light Start
Count Down :Set