2.7
Setting the On/Off hysteresis
Select “
Min.Request
” in the engineering menu, then press the
<Set>
key.
In the upcoming modification dialogue you determine the minimum demand for switching the unit on
(first value) and off (second value) (On/Off hysteresis).
Factory setting:
25/20%
Options:
25/20%
17/12%
Notes on settings
To ensure an optimal current measuring/regulation with electrode based steam generators the hysteresis
is set to 25 % (switch on) and 20 % (switch off).
However you can reduce the hysteresis to 17% (switch on) and 12% (switch off).
2.8
Setting the Stop Mode for bathing operation
With this function you can determine whether or not the <Stop> key is suppressed during bathing operation.
Select “
Stop Mode
” in the engineering menu, then press the
<Set>
key.
In the upcoming modification dialogue you determine whether the bathing time is automatically controlled
via the set bathing time (setting “Timer”) whilst the <Stop> key is suppressed or whether the bathing
time can be stopped at any time by pressing the <Stop> key (setting “Switch”).
Factory setting:
Switch
Options:
Switch
(bathing time can be stopped at any time with the <Stop> key)
Timer
(the bathing time is automatically controlled via the set bathing time, the
<Stop> key is suppressed)
Engineering
Overcurrent :Float
Min.Request :25/20%
Stop Mode :Set
GFCI :Set
Instab.Temp.:Set
Esc
Set
Min.Request
25/20%
17/12%
25/20%
Esc
Set
Stop Mode
Switch
Timer
Switch
Esc
Set
Engineering
Min.Request :25/20%
Stop Mode :Switch
Instab.Temp.:Set
Overcurrent :Float
FactoryReset:Set
Esc
Set