ENGLISH
installation
system reGulations
for Germany only
before installing the boiler, it is necessary to obtain the approval of the main district chimney sweep authorised to submit a chimney calculation.
The appliance must be installed in closed heating systems, that have been installed in accordance with current regulations
and with the
current state of the art.
notes on the installation room
The installation room must:
- comply with local fire regulations and building regulations.
- be frost-proof
- ensure the minimum distances of combustible materials from the boiler wall
moreover, a sufficient supply of fresh air must be guaranteed in the room.
european, national and local installation regulations must be complied with. The combustion air can be supplied through openings to the
outside or, in accordance with safety and installation regulations, from adjacent rooms.
The openings to the outside must be protected against the elements and against the entry of birds or rodents.
The maximum vacuum must not exceed 4Pa in the combustion air inlet system (if present).
If the combustion air is introduced through an opening in the outer wall, a pressure difference of 3 Pa must not be exceeded.
The minimum opening for the combustion air inlet must be at least 100 cm².
requirements for the heatinG water
The heating water must meet the requirements of current hydronic safety regulations.
The lnk-evo log gasification boiler must operate with an anti-condensation valve.
This means that a minimum return temperature of 60°c must be guaranteed to prevent condensation.
If the boIler Is operated wIthout an antI-condensatIon valve, It may be serIously
damaged!
for lnk-evo type boilers, a storage tank must be installed.
check the european, national and local regulations for the size of the storage tank.
The manufacturer recommends the minimum storage tank volumes indicated in the following table:
lnk 15 evo
1000 l
lnk 20 evo
1200 l
lnk 30 evo
1600 l
lnk 40 evo
2100 l
fire protection for installation anD use of thermal Devices
warnIng
In sItuatIons where gases, or flammable vapours may be present,
and In the presence of works wIth a temporary rIsk of fIre or explosIon
(InstallatIon of lInoleum wIth glue, pvc, etc.), the boIlers must be put
In a safe condItIon (swItched off and cooled down) before the danger
arIses.
objects made of flammable materIal must not be placed on the
boIler or closer than the safety dIstance.