Nordic R-09 Installation And Service Manual Download Page 36

11-May-2021 

Page   36 

002512MAN-01 

 

OPERATION TROUBLESHOOTING -  

COOLING MODE

 

Fault 

Possible Cause 

Verification 

Recommended Action 

High Discharge  

pressure 

Unit is overcharged 

(Only possible if unit has 

been field serviced and 

incorrectly charged)  

High subcooling, low delta T across 

water coil. 

Remove 1/2lb of refrigerant at a 

time and verify that the discharge 

pressure reduces.  Or remove 

charge and weigh back in the 

amount listed on nameplate. 

High Suction 

Pressure 

(may appear to 

not be pumping) 

TXV adjusted too far open  Verify superheat.  It should be be-

tween 8-12°F (3-6°C).  Superheat 

will be low if TXV is open too far. 

Adjust TXV to obtain 8-12°F         

(3-6°C) superheat.   

 

TXV stuck open 

Adjusting the TXV does not affect 

the superheat or the suction pres-

sure.  Low super heat and dis-

charge pressure.  

Adjust the TXV all the way in and out a 

few times to loosen it.  Replace TXV  if 

this does not work. 

 

Leaking reversing valve 

Reversing valve is the same tem-

perature on both ends of body,  

common suction line is warm, com-

pressor is running hot. 

Replace reversing valve. 

 

Faulty compressor, not 

pumping 

Pressures change only slightly from 

static values when compressor is 

started. 

Replace compressor. 

Low Suction 

Pressure 

Low airflow 

 

See Fan Troubleshooting section. 

Note:

 low airflow will cause the 

air coil to ice up once the suction 

drops below 

90PSIG

.   

Correct the problem. 

 

TXV stuck almost closed 

or partially blocked by for-

eign object 

Adjusting the TXV does not affect 

the superheat or the suction pres-

sure.  TXV may be frosting up. 

Adjust the TXV all the way in and 

out a few times to loosen it.  Re-

place TXV if this does not work. 

 

Low or no refrigerant 

charge 

Entering air temperature and air-

flow are good but suction is low.  

Check static refrigeration pressure 

of  the unit for a very low value.  

Weigh refrigerant out and compare 

to charge listed on nameplate.  

Locate the leak and repair it.  

Spray 9, a sniffer, and dye are 

common methods of locating a 

leak. 

Compressor 

frosting up 

See Low Suction  

Pressure in this section 

 

 

TXV frosting up 

TXV stuck almost closed 

or partially blocked by for-

eign object. 

Adjusting the TXV does not affect 

the superheat or the suction pres-

sure.   

Adjust the TXV all the way in and out a 

few times to loosen it.  Replace TXV  if 

this does not work. 

Random Low 

Pressure trip  

(does not occur 

while there) 

Faulty compressor       

contactor 

Points pitted or burned.  Contactor 

sometimes sticks causing the com-

pressor to run without the fan, trip-

ping the low pressure control. 

Replace contactor. 

 

Intermittent fan 

See Fan Troubleshooting section. 

Correct the problem. 

Summary of Contents for R-09

Page 1: ...ermal Ltd P O Box 2555 170 Plantation Road Petitcodiac NB E4Z 6H4 506 756 8135 R RH Series Liquid to Air Heat Pumps Single Stage R410a Model Sizes 09 24 info nordicghp com www nordicghp com 002512MAN...

Page 2: ...s serviced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be...

Page 3: ...SDELT SDERT 02 03 R 24 HAC P 1 L C Z SDELT SDERT 02 03 RH 09 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 12 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 18 HAC P 1 3 L C Z SDELT SDERT 04 05 RH 24 HAC P 1 L C...

Page 4: ...Pump Module Installation 21 002336PDG Pump Module Inst 2 Units on 1 Loop 22 Open Loop Installations 23 Well Water Temperature 23 Well Water Flow 23 Well Water Quality 23 Water Discharge Methods 23 Wa...

Page 5: ...Capacity Ratings Ground Water Cooling 60Hz 43 Table 22 Electrical Specifications 47 Table 23 Plenum Heater Electrical Specifications 47 Figure 1 Ground Loop Accessories Tools 16 Figure 2 Open Loop Acc...

Page 6: ...enging water applications check with factory A single thermostatic expansion valve TXV regulates superheat The cabinet is constructed from galvanized sheet metal partly powder coated 1 Heating Mode In...

Page 7: ...acity Ratings rather than detailed performance tables can be used for simplicity For 100 heat pump sizing choose a heat pump with a standard capacity rating that matches or just slightly exceeds the c...

Page 8: ...ill of Materials Open Building Loop Installations FROM MARITIME GEOTHERMAL R RH SERIES HEAT PUMP L OR R RETURN PLENUM HEATER 5 7kW 2H 1C THERMOSTAT OR SOURCED ELSEWHERE P T PORTS AND HOSE ADAPTERS 2 D...

Page 9: ...und wire 6 Install the blower and secure panel with the screws 7 Install the adjacent access panel and secure with the remaining screws Note for both R and RH units for blower motor servicing the enti...

Page 10: ...ce the transformer IMPORTANT NOTE For 208 230VAC 1 60 units if connecting to 208VAC power supply move the red wire connected to the 240 ter minal of the transformer to the 208 terminal of the transfor...

Page 11: ...the 24vac transformer A fault will occur if a conden sate overflow is detected or a low voltage condition electricity grid brownout is detected The control board has an on board LED and an ALR pin wi...

Page 12: ...n external trap and vent must be installed An external condensate pump may be installed if there is not sufficient drain piping slope possible to drain condensate under gravity to its destination To a...

Page 13: ...11 May 2021 Page 13 002512MAN 01...

Page 14: ...Grill Layout Most forced air heating systems have the floor grills placed around the perimeter of the room Supply grills should be placed under a window when possible to help prevent conden sation on...

Page 15: ...11 May 2021 Page 15 002512MAN 01...

Page 16: ...17 16 5 x 16 5 22 944 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 1062 2600 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 24 1227 2900 22 12 x 36 14 x 30 16 x 26 18 x 23 2...

Page 17: ...n be calcu lated in a spreadsheet using the pipe manufacturer s pressure drop tables for pipe diameter and fittings The circulator pump module must be connected to the heat pump Outdoor Loop ports wit...

Page 18: ...utions have been employed in geothermal systems the alcohols such as methanol or ethanol have the most desirable characteristics for groundloop applications The overall heat transfer characteristics o...

Page 19: ...11 May 2021 Page 19 002512MAN 01...

Page 20: ...11 May 2021 Page 20 002512MAN 01...

Page 21: ...11 May 2021 Page 21 002512MAN 01...

Page 22: ...11 May 2021 Page 22 002512MAN 01...

Page 23: ...stream ENSURE SELECTED METHOD CONFORMS TO LOCAL REGULATIONS A return well should be a minimum of 80 ft from the supply well for residential applications The water returned to the well will not necessa...

Page 24: ...pump This reduces the back pressure generated by the weight of the water in the pond Water Valve Water flow through the heat pump is turned on and off by a water valve which is controlled by a 24VAC...

Page 25: ...ld be to install a variable speed submersible pump which varies its speed to maintain a con stant water system pressure Or use a mechanical cycle stop valve which is installed upstream of the air blad...

Page 26: ...11 May 2021 Page 26 002512MAN 01...

Page 27: ...and all the air has been purged as much as possible Further purging may be required after the system has been operating for a while 3 Verify that the loop contains the proper mix of antifreeze for th...

Page 28: ...op Out Supply Out temperature 8 Outdoor Delta T should be between 5 8 F 3 4 C 9 Outdoor flow if available 10 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adju...

Page 29: ...ect and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and...

Page 30: ...the heat exchanger ports and flush the exchanger for several minutes STEP 7 Return the plumbing to its original configuration and open the IN and OUT valves Operate the system and check for improved...

Page 31: ...stat to call for heating or cooling depending on the season STEP 3 If a 24VAC signal does not appear across Y and C of the terminal strip within 6 minutes proceed to the THERMOSTAT TROUBLESHOOTING sec...

Page 32: ...th compressor on See Low Discharge Pressure in Heating Mode Cooling Mode Troubleshooting section Faulty low pressure con trol failed open very unlikely For this test there must be a signal present on...

Page 33: ...Remove wires from compressor Ohmmeter shows infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Re...

Page 34: ...of the flow restriction and correct it Verify pumps are working and sized correctly for ground loop systems Verify well pump and water valve is working for ground water sys tems Entering liquid tempe...

Page 35: ...its Backflush the coaxial exchanger with a calcium removing cleaning solution OPERATION TROUBLESHOOTING HEATING MODE Fault Possible Cause Verification Recommended Action High Suction Pressure may appe...

Page 36: ...r Low Suction Pressure Low airflow See Fan Troubleshooting section Note low airflow will cause the air coil to ice up once the suction drops below 90PSIG Correct the problem TXV stuck almost closed or...

Page 37: ...obes in connector where wire is inserted do not unplug the connect or Recirculation red pin 1 SP1 orange pin 2 SP2 blue pin 3 SP3 brown pin 4 SP4 grey pin 5 If proper signal isn t present re place Fan...

Page 38: ...rocedures to prevent soot buildup inside the pipes It is recommended to replace the liquid line filter dryer any time the refrigeration system has been exposed to the atmosphere Place a wet rag around...

Page 39: ...ontinuously for 2 hours Pump down the unit and replace the filter dryer Vacuum the unit as per above procedure b Charge the unit refrigerant can be re used and operate it for 2 3 days Perform an acid...

Page 40: ...Maximum ELT 80 27 Reduce flow above this temperature Cooling Minimum ELT 41 5 Flow reduction may be required Cooling Maximum ELT 110 43 INDOOR air duct Heating Minimum EAT 60 16 Reduce air flow if nec...

Page 41: ...Drop Data R 18 RH 18 2 5 0 16 0 8 5 5 0 8 5 5 0 9 6 2 1 4 9 7 3 0 19 1 0 6 9 1 1 7 6 1 2 8 3 1 9 13 3 5 0 22 1 4 9 7 1 5 10 1 7 12 2 3 16 4 0 25 1 7 12 1 8 12 2 0 14 2 6 18 4 5 0 28 2 1 15 2 3 16 2 6...

Page 42: ...600 3 9 22 7 6 64 18 1 5 4 5 0 28 3 2 22 1 650 307 935 19 900 5 8 21 4 6 26 24 2 8 0 0 50 4 3 29 7 800 380 931 23 600 6 9 19 6 5 75 Table 19 Standard Capacity Ratings Ground Water Heating 60Hz EAT 68...

Page 43: ...38 4 12 474 5 04 Fan W 82 82 82 82 82 82 82 82 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airflow L...

Page 44: ...7 16 689 4 94 Fan W 104 104 104 104 104 104 104 104 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airfl...

Page 45: ...35 1 22 805 4 91 Fan W 135 135 135 135 135 135 135 135 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp A...

Page 46: ...8 31 015 4 24 Fan W 256 256 256 256 256 256 256 256 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airf...

Page 47: ...ons TABLE 22 Elec Code Power Supply Compressor Fan Out door Circ FLA MCA Max Fuse Breaker Min Wire Size V Hz MIN MAX RLA LRA RLA Max A Amps Amps Amps ga R RH 09 1 208 230 1 60 187 253 4 4 20 2 8 1 5 8...

Page 48: ...11 May 2021 Page 48 002512MAN 01...

Page 49: ...11 May 2021 Page 49 002512MAN 01...

Page 50: ...11 May 2021 Page 50 002512MAN 01...

Page 51: ...11 May 2021 Page 51 002512MAN 01...

Page 52: ...11 May 2021 Page 52 002512MAN 01 Dimensions R 09 12 Left Return...

Page 53: ...11 May 2021 Page 53 002512MAN 01 Dimensions R 09 12 Right Return...

Page 54: ...11 May 2021 Page 54 002512MAN 01 Dimensions R 18 24 Left Return...

Page 55: ...11 May 2021 Page 55 002512MAN 01 Dimensions R 18 24 Right Return...

Page 56: ...11 May 2021 Page 56 002512MAN 01 Dimensions RH 09 12 Left Return...

Page 57: ...11 May 2021 Page 57 002512MAN 01 Dimensions RH 09 12 Right Return...

Page 58: ...11 May 2021 Page 58 002512MAN 01 Dimensions RH 18 24 Left Return...

Page 59: ...11 May 2021 Page 59 002512MAN 01 Dimensions RH 18 24 Right Return...

Page 60: ...hed and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It is the customer s responsibi...

Reviews: