Nordic R-09 Installation And Service Manual Download Page 18

11-May-2021 

Page   18 

002512MAN-01 

 

TABLE 12 - Volume of fluid per 100 ft. of pipe

 

 

Volume /100ft.

 

Type of Pipe

 

Diameter

 

 I.gal 

 

gal 

Copper 

1” 

3.4 

4.1 

15.5 

 

1-1/4” 

5.3 

6.4 

24.2 

 

1-1/2” 

7.7 

9.2 

34.8 

Rubber Hose 

1” 

3.2 

3.9 

14.8 

Polyethylene 

3/4” IPS SDR11 

2.3 

2.8 

10.6 

 

1” IPS SDR11 

3.7 

4.5 

17.0 

 

1-1/4” IPS SDR11 

6.7 

8.0 

30.3 

 

1-1/2” IPS SDR11 

9.1 

10.9 

41.3 

 

2” IPS SDR11 

15.0 

18.0 

68.1 

Other  Item Volumes 

Heat Exchanger 

Average 

1.2 

1.5 

5.7 

Purge Cart Tank  See cart manual 

TBD  

TABLE 11 - Antifreeze Percentages 

 

BY VOLUME 

Protection to: 

10°F 

15°F 

20°F 

25°F 

Methanol 

25% 

21% 

16% 

10% 

Propylene Glycol 

38% 

30% 

22% 

15% 

Protection to: 

10°F 

15°F 

20°F 

25°F 

Methanol  16.8% 

13.6% 

10% 

6.3% 

Propylene Glycol 

30% 

23.5% 

18.3% 

12.9% 

BY WEIGHT 

pressure before actual water pressure is put on the system . 

Systems without an expansion tank will experience greater fluc-

tuations in pressure between the heating and cooling seasons, 

causing pressure gauges to have different values as the loop 

temperature changes.  This fluctuation is normal since 

expansion and contraction of the loop fluid must be handled by 

the elasticity of the plastic loop. 

 



Pressurize the loop to a static pressure of 

45 psig

. when 

installing a system in the fall going into the heating season. 



Pressurize the loop to a static pressure of 

25 psig

. when 

installing a system in the spring or summer going into the 

cooling season.  

 

After operating the heat pump for a period of time, any 

residual air in the system should be bled off and the static pres-

sure should be verified and adjusted if necessary. Add 

additional water / antifreeze mix with the purge cart to bring the 

pressure back to the original setting if required. 

 

Pipe Insulation  

 

All ground loop piping  inside the structure (between the 

structure entry point and the heat pump) should be insulated 

with 3/8”  thick closed cell pipe insulation to prevent condensa-

tion and dripping onto floors or walls. 

 

Low Pressure Control Selection  

 

The purpose of the low pressure control is prevent heat 

exchanger freezing in the case of a flow problem.

 

 

Unlike other NORDIC model series, low pressure control 

selection for open loop for the R/RH 09-24 is done manually, 

with a wire jumper.  For closed loops with antifreeze, make sure 

a jumper is connected between 

LP1 

and 

LP2 

on the heat 

pump’s terminal strip.  This will cause the lower 55 psi low pres-

sure control to be selected, to allow a lower loop temperature 

than would be appropriate for fresh water before tripping.  

 

Although many different antifreeze solutions have been 

employed in geothermal systems, the alcohols such as 

methanol or ethanol have the most desirable characteristics for 

groundloop applications. The overall heat transfer 

characteristics of these fluids remain high although care must be 

taken when handling pure alcohols since they are extremely 

flammable. Once mixed in a typical 25% by volume ratio with 

water the solution is not flammable. In situations where alcohols 

are not allowed as a loop fluid due to local regulations then 

propylene glycol is a non-toxic alternative which can be 

substituted . Propylene glycol should only be used in cases 

where alcohols are not permitted since the heat transfer 

characteristics are less desirable and it becomes more viscous 

at low temperatures, increasing pumping power.  

 

    The volume of fluid that your loop system holds can be 

closely estimated by totaling the number of ft. of each size pipe 

in the system and referencing the following table for 

approximate volume per 100 ft. 

 

When the volume of the loop has been calculated and the 

appropriate amount of antifreeze is ready for addition by 

referencing the table, drain the equivalent amount of water from 

the flush cart or mixing barrel and replace it with the antifreeze. 

 

When using alcohols, be sure to inject below the water 

line to reduce initial volatility of the pure antifreeze. 

If the 

loop is large it may be necessary to refill the tank with antifreeze 

several times to get all the antifreeze into the loop. Pump the 

loop for 5 to 10 minutes longer to ensure the remaining fluid has 

been well mixed. 

 

Initial Pressurization 

At this point open all valves in the flow circuit and slowly 

close off the supply and return flush cart valves in a manner that 

leaves about  

20-30 psig

. on the system. If an air bladder 

expansion tank is used it should be charged to the above 

Adding Antifreeze Solution 

In most mid and northern areas of the US and in all of 

Canada it is necessary to condition the loop fluid by the addition 

of some type of antifreeze solution so that it will not freeze 

during operation in the winter months. This antifreeze is required 

because the loop fluid will normally reach a low entering 

temperature of 

28°F to 32°F (-2°C to 0°C)

 and refrigerant 

temperatures inside the heat pump’s heat exchanger may be as 

low as 

20°F (11°C) 

cooler. See following table

 

for details of 

freeze protection provided by different concentrations.  

 

WARNING: Add enough antifreeze to allow 

for a temperature 20°F (11°C) lower than the 

expected lowest loop fluid temperature 

entering the heat pump.  Insufficient anti-

freeze concentration could cause the heat 

exchanger to freeze and rupture, voiding the 

warranty. 

Summary of Contents for R-09

Page 1: ...ermal Ltd P O Box 2555 170 Plantation Road Petitcodiac NB E4Z 6H4 506 756 8135 R RH Series Liquid to Air Heat Pumps Single Stage R410a Model Sizes 09 24 info nordicghp com www nordicghp com 002512MAN...

Page 2: ...s serviced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be...

Page 3: ...SDELT SDERT 02 03 R 24 HAC P 1 L C Z SDELT SDERT 02 03 RH 09 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 12 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 18 HAC P 1 3 L C Z SDELT SDERT 04 05 RH 24 HAC P 1 L C...

Page 4: ...Pump Module Installation 21 002336PDG Pump Module Inst 2 Units on 1 Loop 22 Open Loop Installations 23 Well Water Temperature 23 Well Water Flow 23 Well Water Quality 23 Water Discharge Methods 23 Wa...

Page 5: ...Capacity Ratings Ground Water Cooling 60Hz 43 Table 22 Electrical Specifications 47 Table 23 Plenum Heater Electrical Specifications 47 Figure 1 Ground Loop Accessories Tools 16 Figure 2 Open Loop Acc...

Page 6: ...enging water applications check with factory A single thermostatic expansion valve TXV regulates superheat The cabinet is constructed from galvanized sheet metal partly powder coated 1 Heating Mode In...

Page 7: ...acity Ratings rather than detailed performance tables can be used for simplicity For 100 heat pump sizing choose a heat pump with a standard capacity rating that matches or just slightly exceeds the c...

Page 8: ...ill of Materials Open Building Loop Installations FROM MARITIME GEOTHERMAL R RH SERIES HEAT PUMP L OR R RETURN PLENUM HEATER 5 7kW 2H 1C THERMOSTAT OR SOURCED ELSEWHERE P T PORTS AND HOSE ADAPTERS 2 D...

Page 9: ...und wire 6 Install the blower and secure panel with the screws 7 Install the adjacent access panel and secure with the remaining screws Note for both R and RH units for blower motor servicing the enti...

Page 10: ...ce the transformer IMPORTANT NOTE For 208 230VAC 1 60 units if connecting to 208VAC power supply move the red wire connected to the 240 ter minal of the transformer to the 208 terminal of the transfor...

Page 11: ...the 24vac transformer A fault will occur if a conden sate overflow is detected or a low voltage condition electricity grid brownout is detected The control board has an on board LED and an ALR pin wi...

Page 12: ...n external trap and vent must be installed An external condensate pump may be installed if there is not sufficient drain piping slope possible to drain condensate under gravity to its destination To a...

Page 13: ...11 May 2021 Page 13 002512MAN 01...

Page 14: ...Grill Layout Most forced air heating systems have the floor grills placed around the perimeter of the room Supply grills should be placed under a window when possible to help prevent conden sation on...

Page 15: ...11 May 2021 Page 15 002512MAN 01...

Page 16: ...17 16 5 x 16 5 22 944 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 1062 2600 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 24 1227 2900 22 12 x 36 14 x 30 16 x 26 18 x 23 2...

Page 17: ...n be calcu lated in a spreadsheet using the pipe manufacturer s pressure drop tables for pipe diameter and fittings The circulator pump module must be connected to the heat pump Outdoor Loop ports wit...

Page 18: ...utions have been employed in geothermal systems the alcohols such as methanol or ethanol have the most desirable characteristics for groundloop applications The overall heat transfer characteristics o...

Page 19: ...11 May 2021 Page 19 002512MAN 01...

Page 20: ...11 May 2021 Page 20 002512MAN 01...

Page 21: ...11 May 2021 Page 21 002512MAN 01...

Page 22: ...11 May 2021 Page 22 002512MAN 01...

Page 23: ...stream ENSURE SELECTED METHOD CONFORMS TO LOCAL REGULATIONS A return well should be a minimum of 80 ft from the supply well for residential applications The water returned to the well will not necessa...

Page 24: ...pump This reduces the back pressure generated by the weight of the water in the pond Water Valve Water flow through the heat pump is turned on and off by a water valve which is controlled by a 24VAC...

Page 25: ...ld be to install a variable speed submersible pump which varies its speed to maintain a con stant water system pressure Or use a mechanical cycle stop valve which is installed upstream of the air blad...

Page 26: ...11 May 2021 Page 26 002512MAN 01...

Page 27: ...and all the air has been purged as much as possible Further purging may be required after the system has been operating for a while 3 Verify that the loop contains the proper mix of antifreeze for th...

Page 28: ...op Out Supply Out temperature 8 Outdoor Delta T should be between 5 8 F 3 4 C 9 Outdoor flow if available 10 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adju...

Page 29: ...ect and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and...

Page 30: ...the heat exchanger ports and flush the exchanger for several minutes STEP 7 Return the plumbing to its original configuration and open the IN and OUT valves Operate the system and check for improved...

Page 31: ...stat to call for heating or cooling depending on the season STEP 3 If a 24VAC signal does not appear across Y and C of the terminal strip within 6 minutes proceed to the THERMOSTAT TROUBLESHOOTING sec...

Page 32: ...th compressor on See Low Discharge Pressure in Heating Mode Cooling Mode Troubleshooting section Faulty low pressure con trol failed open very unlikely For this test there must be a signal present on...

Page 33: ...Remove wires from compressor Ohmmeter shows infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Re...

Page 34: ...of the flow restriction and correct it Verify pumps are working and sized correctly for ground loop systems Verify well pump and water valve is working for ground water sys tems Entering liquid tempe...

Page 35: ...its Backflush the coaxial exchanger with a calcium removing cleaning solution OPERATION TROUBLESHOOTING HEATING MODE Fault Possible Cause Verification Recommended Action High Suction Pressure may appe...

Page 36: ...r Low Suction Pressure Low airflow See Fan Troubleshooting section Note low airflow will cause the air coil to ice up once the suction drops below 90PSIG Correct the problem TXV stuck almost closed or...

Page 37: ...obes in connector where wire is inserted do not unplug the connect or Recirculation red pin 1 SP1 orange pin 2 SP2 blue pin 3 SP3 brown pin 4 SP4 grey pin 5 If proper signal isn t present re place Fan...

Page 38: ...rocedures to prevent soot buildup inside the pipes It is recommended to replace the liquid line filter dryer any time the refrigeration system has been exposed to the atmosphere Place a wet rag around...

Page 39: ...ontinuously for 2 hours Pump down the unit and replace the filter dryer Vacuum the unit as per above procedure b Charge the unit refrigerant can be re used and operate it for 2 3 days Perform an acid...

Page 40: ...Maximum ELT 80 27 Reduce flow above this temperature Cooling Minimum ELT 41 5 Flow reduction may be required Cooling Maximum ELT 110 43 INDOOR air duct Heating Minimum EAT 60 16 Reduce air flow if nec...

Page 41: ...Drop Data R 18 RH 18 2 5 0 16 0 8 5 5 0 8 5 5 0 9 6 2 1 4 9 7 3 0 19 1 0 6 9 1 1 7 6 1 2 8 3 1 9 13 3 5 0 22 1 4 9 7 1 5 10 1 7 12 2 3 16 4 0 25 1 7 12 1 8 12 2 0 14 2 6 18 4 5 0 28 2 1 15 2 3 16 2 6...

Page 42: ...600 3 9 22 7 6 64 18 1 5 4 5 0 28 3 2 22 1 650 307 935 19 900 5 8 21 4 6 26 24 2 8 0 0 50 4 3 29 7 800 380 931 23 600 6 9 19 6 5 75 Table 19 Standard Capacity Ratings Ground Water Heating 60Hz EAT 68...

Page 43: ...38 4 12 474 5 04 Fan W 82 82 82 82 82 82 82 82 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airflow L...

Page 44: ...7 16 689 4 94 Fan W 104 104 104 104 104 104 104 104 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airfl...

Page 45: ...35 1 22 805 4 91 Fan W 135 135 135 135 135 135 135 135 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp A...

Page 46: ...8 31 015 4 24 Fan W 256 256 256 256 256 256 256 256 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airf...

Page 47: ...ons TABLE 22 Elec Code Power Supply Compressor Fan Out door Circ FLA MCA Max Fuse Breaker Min Wire Size V Hz MIN MAX RLA LRA RLA Max A Amps Amps Amps ga R RH 09 1 208 230 1 60 187 253 4 4 20 2 8 1 5 8...

Page 48: ...11 May 2021 Page 48 002512MAN 01...

Page 49: ...11 May 2021 Page 49 002512MAN 01...

Page 50: ...11 May 2021 Page 50 002512MAN 01...

Page 51: ...11 May 2021 Page 51 002512MAN 01...

Page 52: ...11 May 2021 Page 52 002512MAN 01 Dimensions R 09 12 Left Return...

Page 53: ...11 May 2021 Page 53 002512MAN 01 Dimensions R 09 12 Right Return...

Page 54: ...11 May 2021 Page 54 002512MAN 01 Dimensions R 18 24 Left Return...

Page 55: ...11 May 2021 Page 55 002512MAN 01 Dimensions R 18 24 Right Return...

Page 56: ...11 May 2021 Page 56 002512MAN 01 Dimensions RH 09 12 Left Return...

Page 57: ...11 May 2021 Page 57 002512MAN 01 Dimensions RH 09 12 Right Return...

Page 58: ...11 May 2021 Page 58 002512MAN 01 Dimensions RH 18 24 Left Return...

Page 59: ...11 May 2021 Page 59 002512MAN 01 Dimensions RH 18 24 Right Return...

Page 60: ...hed and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It is the customer s responsibi...

Reviews: