Nordic R-09 Installation And Service Manual Download Page 14

11-May-2021 

Page   14 

002512MAN-01 

 

Ductwork 

Blower Motor

 

The indoor unit is equipped with a direct drive 5-speed 

ECM blower.  See Wiring chapter for description and airflow 

adjustment.

 

 

Duct Systems - General 

 

Ductwork layout for a heat pump will differ from traditional 

hot air furnace design in the number of leads and size of main 

trunks required. Air temperature leaving the heat pump is 

normally 

95º -105ºF (35-40ºC)

, much cooler than that of a 

conventional fossil fuel furnace. To compensate for this, larger 

volumes of lower temperature air must be moved and 

consequently duct sizing must be able to accommodate the 

greater airflow without creating a high static pressure or high 

velocity at the floor diffusers.  

 

A duct system capable of supplying the required airflow is 

of utmost importance.  Maritime Geothermal Ltd. recommends 

that the external static pressure from the duct system be kept 

below 0.2 inches of water total.  In some instances the number 

of floor diffusers will actually double when compared to the 

number that would be used for a hot air oil-fired furnace.  Refer 

to following tables. 

 

 

1.  Generally allow 

100 cfm 

for each floor grill. 

2.  All leads to the grills should be 6'' in diameter (28sq.in. each). 

3.  The main hot air trunks should be at least 75% of the square      

     surface area of leads being fed at any given point. 

4.  Return air grills should have a minimum of the same total   

     square surface area as the total of the supply grills.  

5.  The square surface area of the return trunks should equal   

     the square surface area of the grills being handled at any   

     given point along the trunk. 

 

It is 

VERY IMPORTANT

 

that all turns in both the supply 

trunks and the return trunks be made with 

TURNING RADII

. Air 

act like a fluid and, just like water, pressure drop is increased 

when air is forced to change direction rapidly around a sharp or 

irregular corner. 

 

It is recommended that flexible collars be used to connect 

the main trunks to the heat pump.  This helps prevent any vibra-

tions from travelling down the ductwork.  If a plenum heater is 

installed, the collar should be at least 12” away from the heater 

elements. 

 

If desired, the first 5-10 feet of the main supply trunks can  

be insulated internally with acoustical duct insulation to further 

inhibit any noise from the unit from travelling down the ductwork.  

If a plenum heater is installed, insulation should not be placed 

within 12” of the heater elements. 

Duct Systems - Grill Layout 

    

 

Most forced air heating systems have the floor grills placed 

around the perimeter of the room.   Supply grills should be 

placed under a window when possible to help prevent conden-

sation on the window.  As mentioned in the previous sub-

section, supply grill leads should be 6'' in diameter (28 square 

inches each) to allow 

100 cfm

 of airflow. 

 

In a typical new construction, there should be one supply 

grill for every 100 square feet of area in the room.  When rooms 

require more than one grill, they should be placed in a manner 

that promotes even heat distribution, such as one at each end of  

the room.  It is always a good idea to place a damper in each 

grill supply or place adjustable grills so that any imbalances in 

the heat distribution can be corrected. 

 

The total number of supply grills available is based on the 

heat pump nominal airflow.  The table

 

shows the number of 

grills recommended per heat pump size. 

Return grills should be mounted on the floor.  At minimum 

they should be the same size as the supply grill, 

it is highly rec-

ommended that they be 25% to 50% larger than the total 

supply.

 They should be placed opposite the supply grills 

when possible to ensure distribution across the room.  For 

rooms requiring more than one supply grill, it may be possible to 

use one larger return grill if it can be centrally positioned oppo-

site of the supply grills, however it is preferred to have one re-

turn for each supply to optimize heat distribution across the 

room. 

 

Thermostat Location 

 

Most small installations are a single ducted air zone with 

one thermostat.  The thermostat should be centrally located 

within the space, typically on the main floor.  It should be placed 

away from any supply grills, and should not be positioned direct-

ly above a return grill.  The thermostat can be located in a hall-

way, or on the inner wall of a room.  It should be noted that most  

buildings not have any supply ducts in the hallway.  This can 

lead to a temperature lag at the thermostat if there is very little 

air movement in the hallway, causing the space to be warmer 

than indicated by the thermostat. 

 

Plenum Heater

 

As described in the 

Installation Basics 

section, the plenum 

heater will be installed in the discharge ductwork outside the 

unit, at least 12” away from any flexible duct collars.  There is an 

accessory plenum heater with a wider cage profile available that 

is more suitable for duct installation than the model with the nar-

rower cage which is meant for internal installation in larger heat 

pumps. 

TABLE 9 - Heat Pump Size vs.  Hot Air Grills 

Model

 

Size (tons) 

# of Grills (@100 cfm)

 

09 

0.75 

12 

18 

1.5 

24 

Summary of Contents for R-09

Page 1: ...ermal Ltd P O Box 2555 170 Plantation Road Petitcodiac NB E4Z 6H4 506 756 8135 R RH Series Liquid to Air Heat Pumps Single Stage R410a Model Sizes 09 24 info nordicghp com www nordicghp com 002512MAN...

Page 2: ...s serviced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be...

Page 3: ...SDELT SDERT 02 03 R 24 HAC P 1 L C Z SDELT SDERT 02 03 RH 09 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 12 HAC P 1 3 L C Z SDELT SDERT 03 04 05 RH 18 HAC P 1 3 L C Z SDELT SDERT 04 05 RH 24 HAC P 1 L C...

Page 4: ...Pump Module Installation 21 002336PDG Pump Module Inst 2 Units on 1 Loop 22 Open Loop Installations 23 Well Water Temperature 23 Well Water Flow 23 Well Water Quality 23 Water Discharge Methods 23 Wa...

Page 5: ...Capacity Ratings Ground Water Cooling 60Hz 43 Table 22 Electrical Specifications 47 Table 23 Plenum Heater Electrical Specifications 47 Figure 1 Ground Loop Accessories Tools 16 Figure 2 Open Loop Acc...

Page 6: ...enging water applications check with factory A single thermostatic expansion valve TXV regulates superheat The cabinet is constructed from galvanized sheet metal partly powder coated 1 Heating Mode In...

Page 7: ...acity Ratings rather than detailed performance tables can be used for simplicity For 100 heat pump sizing choose a heat pump with a standard capacity rating that matches or just slightly exceeds the c...

Page 8: ...ill of Materials Open Building Loop Installations FROM MARITIME GEOTHERMAL R RH SERIES HEAT PUMP L OR R RETURN PLENUM HEATER 5 7kW 2H 1C THERMOSTAT OR SOURCED ELSEWHERE P T PORTS AND HOSE ADAPTERS 2 D...

Page 9: ...und wire 6 Install the blower and secure panel with the screws 7 Install the adjacent access panel and secure with the remaining screws Note for both R and RH units for blower motor servicing the enti...

Page 10: ...ce the transformer IMPORTANT NOTE For 208 230VAC 1 60 units if connecting to 208VAC power supply move the red wire connected to the 240 ter minal of the transformer to the 208 terminal of the transfor...

Page 11: ...the 24vac transformer A fault will occur if a conden sate overflow is detected or a low voltage condition electricity grid brownout is detected The control board has an on board LED and an ALR pin wi...

Page 12: ...n external trap and vent must be installed An external condensate pump may be installed if there is not sufficient drain piping slope possible to drain condensate under gravity to its destination To a...

Page 13: ...11 May 2021 Page 13 002512MAN 01...

Page 14: ...Grill Layout Most forced air heating systems have the floor grills placed around the perimeter of the room Supply grills should be placed under a window when possible to help prevent conden sation on...

Page 15: ...11 May 2021 Page 15 002512MAN 01...

Page 16: ...17 16 5 x 16 5 22 944 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 1062 2600 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 24 1227 2900 22 12 x 36 14 x 30 16 x 26 18 x 23 2...

Page 17: ...n be calcu lated in a spreadsheet using the pipe manufacturer s pressure drop tables for pipe diameter and fittings The circulator pump module must be connected to the heat pump Outdoor Loop ports wit...

Page 18: ...utions have been employed in geothermal systems the alcohols such as methanol or ethanol have the most desirable characteristics for groundloop applications The overall heat transfer characteristics o...

Page 19: ...11 May 2021 Page 19 002512MAN 01...

Page 20: ...11 May 2021 Page 20 002512MAN 01...

Page 21: ...11 May 2021 Page 21 002512MAN 01...

Page 22: ...11 May 2021 Page 22 002512MAN 01...

Page 23: ...stream ENSURE SELECTED METHOD CONFORMS TO LOCAL REGULATIONS A return well should be a minimum of 80 ft from the supply well for residential applications The water returned to the well will not necessa...

Page 24: ...pump This reduces the back pressure generated by the weight of the water in the pond Water Valve Water flow through the heat pump is turned on and off by a water valve which is controlled by a 24VAC...

Page 25: ...ld be to install a variable speed submersible pump which varies its speed to maintain a con stant water system pressure Or use a mechanical cycle stop valve which is installed upstream of the air blad...

Page 26: ...11 May 2021 Page 26 002512MAN 01...

Page 27: ...and all the air has been purged as much as possible Further purging may be required after the system has been operating for a while 3 Verify that the loop contains the proper mix of antifreeze for th...

Page 28: ...op Out Supply Out temperature 8 Outdoor Delta T should be between 5 8 F 3 4 C 9 Outdoor flow if available 10 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adju...

Page 29: ...ect and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and...

Page 30: ...the heat exchanger ports and flush the exchanger for several minutes STEP 7 Return the plumbing to its original configuration and open the IN and OUT valves Operate the system and check for improved...

Page 31: ...stat to call for heating or cooling depending on the season STEP 3 If a 24VAC signal does not appear across Y and C of the terminal strip within 6 minutes proceed to the THERMOSTAT TROUBLESHOOTING sec...

Page 32: ...th compressor on See Low Discharge Pressure in Heating Mode Cooling Mode Troubleshooting section Faulty low pressure con trol failed open very unlikely For this test there must be a signal present on...

Page 33: ...Remove wires from compressor Ohmmeter shows infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Re...

Page 34: ...of the flow restriction and correct it Verify pumps are working and sized correctly for ground loop systems Verify well pump and water valve is working for ground water sys tems Entering liquid tempe...

Page 35: ...its Backflush the coaxial exchanger with a calcium removing cleaning solution OPERATION TROUBLESHOOTING HEATING MODE Fault Possible Cause Verification Recommended Action High Suction Pressure may appe...

Page 36: ...r Low Suction Pressure Low airflow See Fan Troubleshooting section Note low airflow will cause the air coil to ice up once the suction drops below 90PSIG Correct the problem TXV stuck almost closed or...

Page 37: ...obes in connector where wire is inserted do not unplug the connect or Recirculation red pin 1 SP1 orange pin 2 SP2 blue pin 3 SP3 brown pin 4 SP4 grey pin 5 If proper signal isn t present re place Fan...

Page 38: ...rocedures to prevent soot buildup inside the pipes It is recommended to replace the liquid line filter dryer any time the refrigeration system has been exposed to the atmosphere Place a wet rag around...

Page 39: ...ontinuously for 2 hours Pump down the unit and replace the filter dryer Vacuum the unit as per above procedure b Charge the unit refrigerant can be re used and operate it for 2 3 days Perform an acid...

Page 40: ...Maximum ELT 80 27 Reduce flow above this temperature Cooling Minimum ELT 41 5 Flow reduction may be required Cooling Maximum ELT 110 43 INDOOR air duct Heating Minimum EAT 60 16 Reduce air flow if nec...

Page 41: ...Drop Data R 18 RH 18 2 5 0 16 0 8 5 5 0 8 5 5 0 9 6 2 1 4 9 7 3 0 19 1 0 6 9 1 1 7 6 1 2 8 3 1 9 13 3 5 0 22 1 4 9 7 1 5 10 1 7 12 2 3 16 4 0 25 1 7 12 1 8 12 2 0 14 2 6 18 4 5 0 28 2 1 15 2 3 16 2 6...

Page 42: ...600 3 9 22 7 6 64 18 1 5 4 5 0 28 3 2 22 1 650 307 935 19 900 5 8 21 4 6 26 24 2 8 0 0 50 4 3 29 7 800 380 931 23 600 6 9 19 6 5 75 Table 19 Standard Capacity Ratings Ground Water Heating 60Hz EAT 68...

Page 43: ...38 4 12 474 5 04 Fan W 82 82 82 82 82 82 82 82 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airflow L...

Page 44: ...7 16 689 4 94 Fan W 104 104 104 104 104 104 104 104 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airfl...

Page 45: ...35 1 22 805 4 91 Fan W 135 135 135 135 135 135 135 135 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp A...

Page 46: ...8 31 015 4 24 Fan W 256 256 256 256 256 256 256 256 HEATING COOLING OUTDOOR LOOP ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej W Compressor Current A Input Power W EAT C Evap Temp Airf...

Page 47: ...ons TABLE 22 Elec Code Power Supply Compressor Fan Out door Circ FLA MCA Max Fuse Breaker Min Wire Size V Hz MIN MAX RLA LRA RLA Max A Amps Amps Amps ga R RH 09 1 208 230 1 60 187 253 4 4 20 2 8 1 5 8...

Page 48: ...11 May 2021 Page 48 002512MAN 01...

Page 49: ...11 May 2021 Page 49 002512MAN 01...

Page 50: ...11 May 2021 Page 50 002512MAN 01...

Page 51: ...11 May 2021 Page 51 002512MAN 01...

Page 52: ...11 May 2021 Page 52 002512MAN 01 Dimensions R 09 12 Left Return...

Page 53: ...11 May 2021 Page 53 002512MAN 01 Dimensions R 09 12 Right Return...

Page 54: ...11 May 2021 Page 54 002512MAN 01 Dimensions R 18 24 Left Return...

Page 55: ...11 May 2021 Page 55 002512MAN 01 Dimensions R 18 24 Right Return...

Page 56: ...11 May 2021 Page 56 002512MAN 01 Dimensions RH 09 12 Left Return...

Page 57: ...11 May 2021 Page 57 002512MAN 01 Dimensions RH 09 12 Right Return...

Page 58: ...11 May 2021 Page 58 002512MAN 01 Dimensions RH 18 24 Left Return...

Page 59: ...11 May 2021 Page 59 002512MAN 01 Dimensions RH 18 24 Right Return...

Page 60: ...hed and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It is the customer s responsibi...

Reviews: