Unit Startup
The unit is now ready to be started. The steps below outline the procedure for starting the unit and verifying proper operation of
the unit.
It is recommended that safety glasses be worn during the following procedures.
Preparation:
1.
Remove the
caps from the service ports and connect a refrigeration manifold set to the unit.
2.
Turn the power on to the heat pump and set the thermostat to OFF. Set up the thermostat as per the instructions provided
with it so that it will function properly with the heat pump system (set for system type: heat pump). The O
signal should be set to active in cooling mode.
3.
Measure the following voltages on the compressor contactor and record them on the startup sheet: L1-L2, L2-L3, L1-L3.
Heating Mode:
1.
Set the thermostat to heating mode and adjust the setpoint to activate heat pump. The fan should slowly ramp up
to speed after the time delay of the thermostat expires (if applicable) and the compressor will start (allow 30-60 seconds for
the water valve to open for ground water systems)
2.
Check the refrigeration gauges. The suction and discharge pressures will depend on the loop
temperatures, but they should
be about
90-110PSIG
and
260-360PSIG
respectively for a typical start-up.
3.
Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature (poke a small hole in the flex collar and insert probe in airstream)
4. Duct Supply temperature (poke a small hole in the flex collar and insert probe in airstream)
5. Duct Delta T (should be between
22-32°F, 12-18°C
)
6. Outdoor Loop In (Supply In) temperature
7. Outdoor Loop Out (Supply Out) temperature
8. Outdoor Delta T (should be between
5-8°F, 3-4°C
)
9. Outdoor flow (if available)
10. Compressor L1(C) current (black wire, place meter between electrical box and compressor)
4.
Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle.
Record the setpoint,
suction pressure, and discharge pressure when the unit shuts off.
Cooling Mode:
1.
Set the thermostat to cooling mode and adjust the setpoint to activate heat pump.
2.
Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature
4. Duct Supply Out temperature
5. Duct Delta T
6. Outdoor Loop In (Supply In) temperature
7. Outdoor Loop Out (Supply Out) temperature
8. Outdoor Delta T
3.
Adjust the thermostat setpoint to the desired room temperature if possible, otherwise set it just low enough to allow the unit
to run (i.e. 1°F / 0.5°C less than room temperature) and let the unit run through a cycle. Record the thermostat setpoint,
suction pressure and discharge pressure when the unit shuts off.
Final Inspection:
1.
Turn the power off to the unit (and plenum heater if installed) and remove all test equipment.
2.
Install the electrical box cover and the access panel on the heat pump. Install the service port caps securely to prevent
refrigerant loss. Install the electrical cover on the plenum heater if applicable.
3.
Do a final check for leaks in the ground water / ground loop system and ensure the area is clean.
4.
Turn the power on to the unit and the plenum heater if installed. Set the thermostat to the final settings.
Startup Record:
1.
The installer shall sign and date the Startup Record and have the homeowner sign as well. The installer shall leave the Startup
Record with the homeowner, retain a copy for filing and send a copy to Maritime Geothermal Ltd. for warranty registration.
Summary of Contents for R-09
Page 13: ...11 May 2021 Page 13 002512MAN 01...
Page 15: ...11 May 2021 Page 15 002512MAN 01...
Page 19: ...11 May 2021 Page 19 002512MAN 01...
Page 20: ...11 May 2021 Page 20 002512MAN 01...
Page 21: ...11 May 2021 Page 21 002512MAN 01...
Page 22: ...11 May 2021 Page 22 002512MAN 01...
Page 26: ...11 May 2021 Page 26 002512MAN 01...
Page 48: ...11 May 2021 Page 48 002512MAN 01...
Page 49: ...11 May 2021 Page 49 002512MAN 01...
Page 50: ...11 May 2021 Page 50 002512MAN 01...
Page 51: ...11 May 2021 Page 51 002512MAN 01...
Page 52: ...11 May 2021 Page 52 002512MAN 01 Dimensions R 09 12 Left Return...
Page 53: ...11 May 2021 Page 53 002512MAN 01 Dimensions R 09 12 Right Return...
Page 54: ...11 May 2021 Page 54 002512MAN 01 Dimensions R 18 24 Left Return...
Page 55: ...11 May 2021 Page 55 002512MAN 01 Dimensions R 18 24 Right Return...
Page 56: ...11 May 2021 Page 56 002512MAN 01 Dimensions RH 09 12 Left Return...
Page 57: ...11 May 2021 Page 57 002512MAN 01 Dimensions RH 09 12 Right Return...
Page 58: ...11 May 2021 Page 58 002512MAN 01 Dimensions RH 18 24 Left Return...
Page 59: ...11 May 2021 Page 59 002512MAN 01 Dimensions RH 18 24 Right Return...