5-Jul-2022
Page 17
002596MAN-01
POWER SUPPLY TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
No power to the
air handler
Disconnect switch open
(if installed)
Verify disconnect switch is in the
ON position.
Determine why the disconnect
switch was opened, if all is OK
close the switch.
Fuse blown /
breaker tripped
Breaker is tripped at panel; or at air
handler disconnect box, voltmeter
shows 230VAC on the line side but
not on the load side.
Reset breaker or replace fuse with
proper size and type. (Time-delay
type “D”)
No display on
thermostat.
Transformer impedance
protection has been acti-
vated due to a short cir-
cuit, or faulty transformer
230VAC is present across L1 and
L2 of the air handler power strip but
24VAC is not present across R
and
C of the terminal strip.
Replace transformer.
Faulty wiring between air
handler and thermostat
24VAC is not present across R and
C of the thermostat.
Correct the wiring.
Faulty Thermostat
24VAC is present across R and C
of the thermostat but thermostat
has no display.
Replace thermostat.
STEP 1:
If there is a thermostat powered from the air handler’s
R
and
C
terminals, verify that the display is present.
If it is not, proceed to POWER SUPPLY TROUBLESHOOTING; otherwise proceed to STEP 2.
STEP 2:
If a 24VAC signal does not appear across
G
and
C
of the air handler’s terminal strip (or a DC signal across
0-10VDC+
and
GND
for –VSP models) within 6 minutes, proceed to the THERMOSTAT TROUBLESHOOT-
ING section; otherwise, proceed to the FAN/BLOWER TROUBLESHOOTING section.
Troubleshooting Guide
THERMOSTAT TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Incorrect thermostat or
controller setup
Thermostat or controller does not
indicate a call for heating or cooling.
No output signal from thermostat or
controller.
Correct the setup.
Faulty thermostat or con-
troller to air handler wiring
Signal present at output of the ther-
mostat or controller but not present
across G and C (or 0-10VDC+ and
GND) of the air handler’s terminal
strip.
Correct or replace wiring.
Faulty thermostat or con-
troller
No output signal from thermostat or
controller when a demand is indicat-
ed.
Replace thermostat or controller.
No G signal to air
handler
(or 0-10VDC
signal for –VSP
models)
Summary of Contents for AH4P Series
Page 10: ...5 Jul 2022 Page 10 002596MAN 01 ...
Page 26: ...5 Jul 2022 Page 26 002596MAN 01 Wiring Diagram 24VAC Airflow Control ...
Page 27: ...5 Jul 2022 Page 27 002596MAN 01 Wiring Diagram VSP models 0 10VDC Airflow Control ...
Page 28: ...5 Jul 2022 Page 28 002596MAN 01 Dimensions AHW 65 Horizontal Dimensions AHW 65 Vertical ...
Page 29: ...5 Jul 2022 Page 29 002596MAN 01 Dimensions AH4P 65 Horizontal Dimensions AH4P 65 Vertical ...