Troubleshooting - Test C, Motor Start Error
Leave DC supply connected and
remove unit from its enclosure.
Inspect unit ventilation. Max
operational ambient temperature is
131° F (55° C). Is ventilation adequate?
Is the unit free from an overload of hot
items?
START
ŽƌƌĞĐƚǀĞŶƟůĂƟŽŶ
, test unit.
Yes
No
Check the voltage at the DC
connector. Is the voltage within
range?
12 VDC: 10.4 VDC -15.4 VDC
Repair DC supply voltage, test unit.
Yes
No
Is fan running and the coils clean and
not restricted?
Replace power control module.
No
Yes
Replace cooling unit.
Perform Diagnostic Prechecks.
Is unit overloaded?
Reduce load on unit.
Yes
No
NOR000726-4b
Three (3) 1/4 second
fl
ashes, pause,
repeat.
Possible Cause:
The rotor is blocked or the differential
pressure in the refrigeration system is
too high ( >5 bar).
Three 1/4 second flashes, pause, repeat.
Troubleshooting, cont’d.