The
booms
operate
backwards
1.
Ensure
the
raise
lines
are
connected
to
the
“B”
ports
and
the
lower
lines
are
connected
to
the
“A”
ports.
2.
Ensure
the
electrical
connections
are
correct.
3.
Ensure
the
valves
are
configured
(mapped)
correctly.
The
booms
move
too
fast
or
too
slow
1.
Ensure
the
orifices
are
installed
correctly.
If
the
“B”
port
is
backwards,
the
boom
will
move
up
slowly
and
down
fast.
If
the
“A”
port
is
backwards,
it
will
raise
slowly
and
may
chatter
when
going
down.
2.
Ensure
the
orifices
are
not
jammed
in
the
port.
Try
removing
and
reinstalling
the
orifices.
3.
Check
to
see
if
the
filter
is
plugged.
The
filter
can
be
removed
to
test,
but
it
must
be
reinstalled.
4.
Ensure
the
correct
“A”
and
“B”
port
NORAC
fittings
are
used.
If
the
wrong
fittings
are
used,
the
floating
orifice
may
not
be
operating
correctly.
Summary of Contents for UC5 Topcon X30
Page 1: ...NORAC UC5 Operator s Manual ...
Page 15: ...13 Select the setup button The setup screen will be displayed ...
Page 22: ...20 The automatic setup diagnostic screen is reached by selecting the diagnostics button ...
Page 36: ...34 5 3 Communication Tests ...
Page 41: ...39 Typical Self Propelled Sprayer Installation ...
Page 42: ...40 Typical Pull Type Sprayer Installation ...
Page 43: ...41 Typical Front Mount Sprayer Installation ...
Page 44: ...42 Typical Setup for Short Circuit Test ...
Page 56: ...54 7 UC5 Menu Structure ...
Page 57: ...55 ...
Page 58: ...56 ...
Page 60: ...58 7 2 Setup Valves ...
Page 61: ...59 7 3 Setup Switches Switches ...
Page 67: ...65 10 Notes ...
Page 68: ...66 ...