24
Automatic Dead Zone Calibration:
Follow
Section 8.1.1
(level booms, working RPM, etc.) before proceeding.
Ensure the UC4.5 control panel is in manual mode, at the run screen.
Navigate to the "More?" menu prompt in the SETUP (
) menu. Press
to confirm.
Navigate to the boom section to be set up, for example "Left?" to adjust the left up or the
left down settings. Press the
button to confirm.
Press the
button to access the next menu prompt. Choose the dead zone up or down
setting (
Figure 10
).
Press and hold the
button.
When the "Done" message is displayed, release the
button to view the new setting.
Manual Dead Zone Calibration:
Follow
Section 8.1.1
(level booms, working RPM, etc.) before proceeding.
Ensure the UC4.5 control panel is in manual mode, at the run screen.
Navigate to the "More?" menu prompt in the SETUP (
) menu. Press
to confirm.
Navigate to the boom section to be setup, for example, "Left?" to adjust the left up and/or
the left down settings. Press the
button to confirm.
Press the
button to access the next menu prompt. Choose the dead zone up or down
setting (
Figure 10
).
Press and hold the
button.
The valve will turn on at the indicated setting for exactly one second. The screen will show
the actual change in height.
The change in height reading is live as long as the
button is held. Wait until the height
reading has settled to a stable value and record this reading.
Average three readings. The acceptable average change in height should be from 0.5 to 1.5
inches (13 to 38 mm). Ideal would be 1 inch exactly (25 mm).
If the average is less, increase the DZ setting with the
button. If the average is more,
decrease the DZ setting with the
button.
Repeat the manual dead zone test until the average falls into the acceptable range.