11
Examples of the Modbus settings
The following examples are in the test connection where FT20, TTM20X, Eurotherm 2216e and RMD681
were connected to Modbus line and where Virtual IDs were set as follows.
The device / reading
Slave Address
Virtual IDs
Internal measurements
0…2
FT20
4
3…5
TTM20X
2
6
Eurotherm 2216e
1
7
RMD681
3
8…15
Config / Modbus
Baud rate
19200
Bits
8E1
Timeout[s]
1
Query interval[das]
3
Queries
4
Overview
->
Query 1
->
Query 2
->
Query 3
->
Query 4
->
Example of the Modbus settings for RMD681
Config / Modbus / Query 1
Slave
3
Register Type
Input Register
Register
0
Results
8
Data type
Float LE
Divider
-
Virtual ID
8
Status
OK 25.2
Example of the Modbus settings for FT20
Config / Modbus / Query 2
Slave
4
Register Type
Input Register
Register
1000
Results
3
Data type
Sint 16-bit
Divider
10
Virtual ID
3
Status
OK 15.3
Example of the Modbus settings for TTM20X
Config / Modbus / Query 3
Slave
2
Register Type
Holding Register
Register
0
Results
1