background image

 

10 

 

Config  

 Serial communication 

 Query x   

 Bit field offset  

  

 

 

 

… 

 

15 

The first readable bit of the register when register Data type is Bit Field (starting from the least 
significant bit). 

The number of readable subsequent bits is set in the Results menu. The direction to read starts from 
the least significant bit and continues to the next register. Data Type Bit field gives result of 0 or 1. 

Config   

  Serial communication   

  Query x   

  Divider 

 

 

Off 

 

10 

 

100 

 

1000 

When needed, divides the result with decades (moves comma left). Usable with integers. 

Config   

  Serial communication   

  Query x   

  Virtual ID 

 

The Virtual ID of the first result of the Modbus query. In the Ovaport Measuring points settings the 
"device address" and this virtual ID must match each other. 

Config   

  Serial communication   

  Query x   

  Status 

 

 

Not used (Results setting zero) 

 

OK 

 

Incorrect settings - Conf settings are incorrect 

 

Limited - Only part of the sequential results is fetched, because virtual ID has overlapping with 
some other Modbus query or “internal status” result. 

 

Blocked – The result is not fetched, because virtual ID has overlapping with some other Modbus 

query or “internal status” result. 

 

Unrecognized data - Modbus reply is wrong type or wrong length. 

 

Timeout - Modbus replay was not received. 

 

Exception – Modbus device returned error code. 

 

CRC error 

 

Unknown error 

Overview views Modbus queries and replies status and the first result. For example "OK 24.2", 
"Timeout", CRC error", "Unrecognized data" and so on. 

 

 

Summary of Contents for 98372

Page 1: ...ID8746 V9 22 5 2017 Firmware versions 1 0 1 0 Ovazone Cell Link MTR RS485 3G Manual...

Page 2: ...2 Contents Introduction 3 Installation 4 Configuring the device 7 Usage 16 Maintenance 18 Troubleshooting 19 Specifications 20 Warnings 21 Trademarks 21 Manufacturer 21...

Page 3: ...eliver the data of the radio network to the Ovaport service Each device including nodes and gateways has to be set with the same Ovanet network The Ovanet network number has to be chosen between 1 167...

Page 4: ...lled vertically The base station is splash proof but the location has to be chosen in a way that will not expose it to water or hot steam Please note that the AC socket and the power supply are not sp...

Page 5: ...RS 485 bus D1 pin The diagram below presents the connector pinout looking towards the base station s female connector The same pinout is valid for an opened male connector looking towards the termina...

Page 6: ...S 485 bus cable should no more than 30 meters long The bus is bidirectional Only one device at a time can send data during which other devices listen Only one device connected to the bus is set as mas...

Page 7: ...0 protocol SCL address 0 Programming connector The device has a 3PIN POL programming connector Use POL 3PIN adaptor to connect the DCS772 to the device The 3PIN POL programming connector can be connec...

Page 8: ...t in subsequent registers or they have different data types multiple queries are needed Config Serial communication Overview Not used Results setting zero OK Incorrect settings Conf settings are incor...

Page 9: ...us registers are bit data and the result will be either 0 or 1 Config Serial communication Query x Register Register address search info on this from the other device s manual Config Serial communicat...

Page 10: ...e Modbus query In the Ovaport Measuring points settings the device address and this virtual ID must match each other Config Serial communication Query x Status Not used Results setting zero OK Incorre...

Page 11: ...Timeout s 1 Query interval das 3 Queries 4 Overview Query 1 Query 2 Query 3 Query 4 Example of the Modbus settings for RMD681 Config Modbus Query 1 Slave 3 Register Type Input Register Register 0 Resu...

Page 12: ...vider 10 Virtual ID 6 Status OK 26 8 Example of the Modbus settings for Eurotherm 2216e Config Modbus Query 4 Slave 1 Register Type Input Register Register 1 Results 1 Data type Sint 16 bit Divider Of...

Page 13: ...13 Menu chart...

Page 14: ...14...

Page 15: ...able on request on support nokeval com Mon menu The monitor menu settings are menu settings are mainly for the manufacturer use and most of them are not explained in this manual Support for purpose of...

Page 16: ...low GSM modem has 2G connection Blinks red GSM modem replies Registration denied Solid red GSM modem is unable to communicate with the internal processor SRV Off When there is no IP address Blinks yel...

Page 17: ...low bars Following LEDs are turned off RS485 RF2 RF1 SRV GSM Will return to normal state automatically in 30 s F2 Long press of the multifunction button will trigger an OTA update if update is unsucce...

Page 18: ...h a rubber casket It can be cleaned by wiping with a damp cloth The device is not meant to be immersed into water or other liquids Service If Bat LED indicates low battery voltage red see above BAT LE...

Page 19: ...uccessful The battery level needs to be above certain level to start the search for the new firmware If the search will not start change the battery and try to find a place with a better GSM coverage...

Page 20: ...ffered results Type Non volatile FLASH memory Capacity About 500 000 measurements Battery Type 2 pcs Type D batteries Backup running time About 5 days at 20 C temperature About 8 hours at 20 C tempera...

Page 21: ...t or some other place like in a parked car where temperature can rise to over 50 C The battery may overheat and cause fire or explosion hazard Read this manual carefully before using the device Only N...