Operation mode
The drop-down menu for the operating mode is available here with the options
•
Interval
: The NivuLink Micro goes into sleep mode after every scan to save en-
ergy. The data are transmitted after the configured transmission interval.
•
Permanent
: The NivuLink Micro remains switched on and transmits every
measurement immediately
Additionally, you can activate/deactivate the test mode.
•
Test mode
: once test mode is enabled (= checked) NivuLink Micro will transmit
five measurements directly on the first start-up. This allows you to verify wheth-
er a connection to the server can be set up and whether all settings are correct.
Measuring
1
Entry field for the scan interval in minutes (= measurement interval)
2
Drop-down menu to select transmission periods:
Interval
:
3
= specify the transmission interval in minutes (= interval of data
transmission to communication hub)
Fixed time
:
3
= specify a fixed point in time for daily transmission of data to
the communication hub; format HH:MM (e. g. 14:00)
3
Input field for transmission interval or time (see
2
)
Fig. 7-3: NivuLink Micro configuration tool: Basic settings > Scanning
Sensor
1
Entry field for the warm-up period in seconds
Warm-up period: the time before measurements are taken, when voltage is
applied at the V
sens
output.
2
Opens the drop-down menu to select the sensor voltage.
This is the voltage the sensor needs and which is output via V
sens
.
Fig. 7-4: NivuLink Micro configuration tool: Basic settings > Sensor