Figure 18: Wiring diagram for EVA-UB4 and EVA-UB4-6
SLC Line
impedance is 50Ω at maximum and the maximum length is 2km.
Refer to the manual of control panel NFU-7000 series
to determine correct maximum loop load and maximum loop
resistance for devices connected to each loop.
Use cable AWG12-20 for wiring. Do not connect different gauge cables at one
terminal in order to prevent loosening.
! CAUTION
Do not connect cables in reverse polarity. Failure to connect the polarity correctly
could result in damage to other equipment.
! CAUTION
Figure 19: Correct and incorrect wiring method
For system monitoring
-
For terminals 1 and 6 do not use looped wire under
terminals. Break wire run to provide monitoring of connections.
! CAUTION
Correct wiring
Incorrect wiring