The following figure shows the required heat detector spacing for a 60.9 m (200 ft.) by 60.9 m (200 ft.) room with a 3m
(10 ft.) ceiling. Figure 6 shows 16 heat detectors with the required spacing of S = 15.3 m (50 ft.).
Figure 6: Heat detectors spacing example
10
.7 m
(35
ft.)
15.2 m
(50 ft.)
15.2 m
(50 ft.)
15.2 m
(50 ft.)
1
5
.2
m
(5
0
f
t.
)
1
5
.2
m
(5
0
f
t.
)
1
5.
2
m
(5
0
f
t.
)
7.6 m
(25 ft.)
7.6 m
(25 ft.)
7.6 m
(25 ft.)
7
.6
m
(2
5
f
t.
)
6
0
.9
m
(
2
0
0
f
t.
)
60.9 m (200 ft.)