EV-Mini IP2 Installation instructions
IIS-EV-Mini IP2 Issue 4 18/01/2019
NOTES:
General Operation
Standby condition: The module receives polling from the control panel at the regular
interval.
Input condition: When the monitored contact switches into an input state, the module
reports the state to the control panel.
Fault condition: The module reports to the control panel on an open or short circuit in the
input circuit.
SCI in active condition: When SCI is activated to isolate a short circuit in the loop, the LED
on the module illuminates yellow.
Compatible Remote LED Indicator
The EV-Mini IP2 is compatible with Nittan remote LED indicator: STA-R1
Interchangeability with Existing Products
It is necessary to update the firmware of the control panel to respond to EV-Mini IP2, prior
to the replacement of the existing model EV-Mini IP. The EOL resistors will also need to be
changed.
SCI Function
The EV-Mini IP2 has a built-in short circuit isolator. The SCI circuit prevents entire loop failure
in the event of a short between L+ and L- on the loop. If a short circuit is detected, the
section of line containing a short circuit is automatically isolated.
Service and Maintenance
Inspection and tests of the module shall be carried out periodically according to the
requirements of BS 5839 Part 1, Fire Detection and Alarm Systems for Buildings: Code of
Practice for System Design, Installation and Servicing, or equivalent local codes of
practice.
For a routine inspection, ensure the module is secure and undamaged.
When carrying out site testing of the module, set the Fire Alarm Control Panel to test mode
and take any necessary precautions, so as to limit the activation of alarm sounders/bells
and any fire service summoning device.