EV-Mini IP2 Installation instructions 

 

IIS-EV-Mini IP2 Issue 4 18/01/2019 

NOTES: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

General Operation 

Standby condition: The module receives polling from the control panel at the regular 
interval. 

Input condition: When the monitored contact switches into an input state, the module 
reports the state to the control panel. 

Fault condition: The module reports to the control panel on an open or short circuit in the 
input circuit. 

SCI in active condition: When SCI is activated to isolate a short circuit in the loop, the LED 
on the module illuminates yellow. 

Compatible Remote LED Indicator 

The EV-Mini IP2 is compatible with Nittan remote LED indicator: STA-R1 

Interchangeability with Existing Products 

It is necessary to update the firmware of the control panel to respond to EV-Mini IP2, prior 
to the replacement of the existing model EV-Mini IP. The EOL resistors will also need to be 
changed. 

SCI Function 

The EV-Mini IP2 has a built-in short circuit isolator. The SCI circuit prevents entire loop failure 
in the event of a short between L+ and L- on the loop. If a short circuit is detected, the 
section of line containing a short circuit is automatically isolated. 

Service and Maintenance  

Inspection and tests of the module shall be carried out periodically according to the 
requirements of BS 5839 Part 1, Fire Detection and Alarm Systems for Buildings: Code of 
Practice for System Design, Installation and Servicing, or equivalent local codes of 
practice. 

For a routine inspection, ensure the module is secure and undamaged. 

When carrying out site testing of the module, set the Fire Alarm Control Panel to test mode 
and take any necessary precautions, so as to limit the activation of alarm sounders/bells 
and any fire service summoning device. 

 

 

 

 

 

 

 