background image

EV-Mini IP2 Installation instructions 

 

IIS-EV-Mini IP2 Issue 4 18/01/2019 

RoHS Compliance Statement  

This product complies with the European Union RoHS (Restriction of Hazardous Substances) 
directive 2011/65/EU which restricts the use of the following six hazardous materials in the 
manufacture of electronic and electrical equipment. 
• Lead (Pb) 
• Hexavalent Chromium 
• Mercury (Hg) 
• Cadmium (Cd) 
• Polybrominated biphenyls (PBB’s) 
• Polybrominated diphenyl ethers (PBDE’s) 

 

 

NOTE:

 Please read these instructions carefully and keep for future reference. The 

information in this document is subject to change without notice. For updates please refer 
to our website. 

NOTE:

 Follow the requirements for the installation of the product in accordance with the 

Specifications. Otherwise it may cause malfunction 

NOTE:

 Do not install the product in any location where oil, dust, iron powder, chemicals, or 

hydrogen sulphide may occur or affect the product. It may cause malfunction. 

This package contains the following items

Main unit: 

x 1 

EOL resistor:  

10k ohm x 1 

Alarm Resistor:  

680 ohm x 1 

Manual:   

(this document) x 1 

General Description

 

The EV-Mini IP2 Mini Input Module is a compact size addressable input module with short 
circuit isolator. The module provides the function to monitor an input from manual call 
points, aspirating smoke detectors, beam detectors, ventilation control and fire door 
control systems, etc. 

The EV-Mini IP2 provides one input circuit (Class B) that can be connected to input 
devices with a normally open dry contact. The EV-Mini IP2 monitors the dry contact input 
through a 10k EOL resistor. The monitoring state (normal, input, open, or short) of the 
device is transmitted to the control panel.  

The module is equipped with a constant current output (2.5mA typ.) for a remote 
indicator, which allows the remote indicator STA-R1 to be connected. 

 

 

 
 
 
 
 
 
 
 
 

 

 
 
 

EV-Mini IP2 – Mini Input Module 

with Isolator 

EN 54-17: 2005 / AC: 2007 – Short Circuit Isolators 

EN 54-18: 2005 / AC: 2007 – Input / Output Devices 

 

         

  

19 

 

0359 

 

For use with Nittan Evolution Protocol Only. 

Loop Voltage: 20 to 38 Vdc 

Quiescent Current: 690µA 

Alarm Current: 3.3mA (Inc. LED) 

Loop resistance

< 50 ohm/ km 

Input line resistance

::::

 < 50 ohm/ km 

EOL resistor: 10k ohm 

Input resistance: 470 ohm or 680 ohm 

Input threshold level: ON

< 680 ohm, 

                                      Short

<50 ohm,  

                                        Open

> 20k ohm 

Min sw open voltage (Vso min): 11 Vdc 

Max sw open voltage (Vso max): 14 Vdc 

Min sw close voltage (Vsc min): 3 Vdc 

Max sw close voltage (Vsc max): 10 Vdc 

Max line current (Ic max): 500 mA 

Max switching current (Is max): 1500 mA 

Max leakage current (Il max): 15 mA 

Max switch resistance (Zc max): 150 m

Ω

 

Wire size: Min. 0.75mm

2

 

                 Max. 2.5mm

2

 

Operating temperature: -10

°

C to 55

°

Storage temperature: -40

°

C to 80

°

Max. relative humidity: 95%RH, non-condensing 

Mass: 40g 

 