Trouble shooting  

 

Problem 

Possible cause 

No response  

The module falls off.  
Address setting is not correct. Duplicate address. 
Loop wiring is not correct. An open or short circuit in the 

loop. 

Loop voltage is too low. 

Communication error 

Duplicate address. 
Loop voltage is too low. 

The module information is not 
found on the panel 

Data registered on the control panel is not correct. 

Open circuit is detected in 
the input circuit 

Input wiring is not correct. An open circuit in the input 
circuit. 
EOL resistor is removed. 

Short circuit is detected in the 
input circuit 

Input wiring is shorted. 
 

Input condition is latched 

Insulation in the input circuit is not enough. Input wiring is 
not correct. EOL resistor is not appropriate. 

Input is not detected 

Input wiring is not correct. 
Input resistor is not appropriate. 

Short circuit is detected in the 
input condition 

Input wiring is not correct. Input resistor is not connected. 

SCI operates 

There is a short circuit in the loop. 
Too many devices (over 20mA in total in a standby 
condition) are connected between the module and the 
next SCI.  

 

 

 

 

 

 

 

 

Dimensions 

 

 

End of Life Disposal 

Like all electronic equipment, at the end of its working life this unit should not be disposed 
of in a refuse bin. All Nittan products since 2005 have been marked with the WEEE Logo in 
compliance with European Directive 2012/19/EU and Nittan Europe Limited is a member 
of a WEEE Compliance Scheme. Contact [email protected] for a copy of our WEEE 