EV-Mini IP2 Installation instructions 

 

IIS-EV-Mini IP2 Issue 4 18/01/2019 

Address Setting 

Use EV-AD2-EXT to set the address of the EV-Mini IP2. The factory default address of 1 is 
given to the module. Connect the EV-AD2-EXT to the address setting port with the Micro 
USB cable for the programmer, and change the address to any of 1-254, with reference to 
the instruction manual of EV-AD2-EXT programmer.  (Note that the number of available 
addresses can be less depending on a control panel model.) The address can be set 
regardless of whether power supply from the control panel is turned on or off. 

Address setting is possible even after connecting the module to the Loop. 

Installation 

This compact size allows it to fit inside UK 1-gang boxes (Min 35mm depth) or devices such 
as manual call points and aspirating smoke detectors. Use the mounting tabs to secure 
the module to the 1 gang box. To install the EV- Mini IP2 in aspirating smoke detectors or 
beam-type smoke detectors, cut off the mounting tabs if necessary.

     

 
 
 
 
 
 
 
 
 
 
 

 

Connections 

 

 

NOTES: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2 

Figure 3 

 

Mounting Screw 

EV-Mini IP2 

35mm 1-gang box 

Mounting Tab 