background image

User's Guide for CTS6000 Control panel 

 

Version 1.00 

Subject to alteration without notice.  

NILAN A/S 

Page 10 of 11  

Description of alarms 

Alarm name 

Description 

Remedy 

Door open 
ID 32        Level - 4 

Door  to  fans  is  open.  Ventilation  unit 
stops in order to prevent personal injury.  

Close door and reset alarm. 

Fire alarm 
 
 
 
ID 33        Level - 4 

The  unit  is  equipped  with  two  fire 
thermostats:  one  in  the  inlet  duct,  the 
other in the exhaust duct. If temperature 
becomes excessive, the thermostats are 
activated.  

Reset  fire  thermostats  in  unit 
and reset alarm.  

Smoke alarm 
 
ID 30        Level - 4 

Smoke  detectors  can  be  fitted  in  the 
unit. One of these smoke detectors has 
sensed smoke.  

Check  smoke  detector  and 
reset alarm.  

Thermal relay 
 
 
ID 34        Level - 4 

Motor  protector  has  cut  out;  Klixon  in 
compressor  motor  or  fan  motor  has  cut 
out;  or  error  has  occurred  in  frequency 
converter.  

Reset 

motor 

protector 

or 

remedy  error  in  frequency 
converter and reset alarm.  

High  pressure 
alarm 
 
 
ID 2          Level - 4 

A  high  pressure  alarm  can  be  activated 
if there is insufficient air flow through the 
unit.  This  may  be  caused  by  blocked 
filters,  loose  V-belts  or  dampers  which 
have not opened.  

Reset  alarm.  If  the  alarm 
repeatedly 

occurs 

for 

no 

apparent reason, call service.  

Low  pressure 
alarm 1  
 
 
ID 3 

– 6    Level - 2 

Low pressure alarm 1 can be activated if 
there  is  insufficient  air  flow  through  the 
unit.  This  may  be  caused  by  blocked 
filters,  loose  V-belts  or  dampers  which 
have not opened.  

The 

controls 

stop 

the 

compressor 

itself 

until 

the 

pressure switch is reset. Max. 5 
times an hour, however.  

Condenser  high 
pressure 
 
 
 
 
ID 8 

– 11  Level - 4 

Upper limit(2) for cooling circuit pressure 
set  under  "Pressure  limits"  has  been 
exceeded.  The  alarm  can  be  activated 
by  insufficient  air  flow  through  the  unit. 
This  may  be  caused  by  blocked  filters, 
loose  V-belts  or  dampers  which  have 
not opened.  

Reset  alarm.  If  the  alarm 
repeatedly 

occurs 

for 

no 

apparent reason, call service.  

Evaporator  low 
pressure 1  
 
 
 
 
ID 9 

– 12  Level - 3 

Lower 

limit(2) 

for 

cooling 

circuit 

pressure,  which  is  set  under  "Pressure 
limits",  has  been  exceeded.  The  alarm 
can  be  activated  by  insufficient  air  flow 
through the unit. This may be caused by 
blocked filters, loose V-belts or dampers 
which have not opened.  

The 

controls 

stop 

the 

compressor  until  pressure  is 
regained. Max. 5 times an hour, 
however.  

Evaporator  low 
pressure 2  
ID 10

–13  Level - 4 

Evaporator low pressure 2 is activated if 
Evaporator  low  pressure  1  has  been 
activated 5 times within the last hour.  

Reset  alarm.  If  the  alarm 
repeatedly 

occurs 

for 

no 

apparent reason, call service.  

Condenser 
overheated 
 
 
 
ID 20        Level - 4 

Condenser  temperature  (T5)  setting 
under  "Pressure  limits"  too  high.  The 
alarm can be activated by insufficient air 
flow  through  the  unit.  This  may  be 
caused  by  blocked  filters,  loose  V-belts 
or dampers which have not opened.  

Reset  alarm.  If  the  alarm 
repeatedly 

occurs 

for 

no 

apparent reason, call service.  

Evaporator too cold 
 
 
 
 
ID 21        Level - 4 

Evaporator  temperature  (T6)  setting 
under  "Pressure  limits"  too  low.  The 
alarm can be activated by insufficient air 
flow  through  the  unit.  This  may  be 
caused  by  blocked  filters,  loose  V-belts 
or dampers which have not opened.  

Reset  alarm.  If  the  alarm 
repeatedly 

occurs 

for 

no 

apparent reason, call service.  

All manuals and user guides at all-guides.com

Summary of Contents for CTS6000

Page 1: ...User s Guide CTS6000 control panel Version 1 03 2014 06 25 Valid for SW version 1 0088 All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...oint menu 6 Menu overview 9 Description of alarms 10 Figure Figure 1 Panel startup display 4 Figure 2 Menue 4 Figure 3 Alarm log with new alarm 4 Figure 4 Alarm log with no alarm 4 Figure 5 Power System in Operation 5 Figure 6 Weekly program 5 Figure 7 Selecting the manual set point mode 6 Figure 8 Manual mode parameters setting 7 Figure 9 Manual mode parameters setting 7 Figure 10 Java GUI manual...

Page 3: ... operation to be viewed and altered It is thus possible to change various temperature settings reset alarms and start the unit outside the usual operating period The CTS6000 control panel supplements CTS6000 WebControl the program in which more advanced settings are made A menu overview and descriptions of all alarms can be found at the end of the guide All manuals and user guides at all guides co...

Page 4: ...tup display Figure 2 Menue The startup display reappears if no button is pressed for 15 seconds Alarm log event log The alarm log is accessed by pressing the ALARM button i e the one marked with a bell on the bottom right of the panel The most recent alarms events will then be displayed see Figure 3 It is possible to scroll through previous alarms events using the arrow up and down buttons Figure ...

Page 5: ...hen press arrow right to open the weekly program see Figure 6 Use arrow up or arrow down to scroll through the various menu options for the day selected As standard Monday is initially displayed when the weekly program is opened Six program events can be defined for each day of the week Figures at the top of the display indicate the number of events defined for the day in question For each program...

Page 6: ...access the service menu activate the control panel by pressing arrow down Then press and hold SET for approx 10 seconds The service menu will then appear Manuel Set point menu To enter the manual set point mode one should hold power button until the corresponding menu appears see Figure 7 Selecting the manual set point mode After selecting the mode one is able to adjust manual mode parameters see ...

Page 7: ...ter 2 Parameters editing a Button SET start of value editing b Buttons Up Down change a value 1 1 c Button Left cancel editing d Button SET store a changed value 3 Return back from menu sub menu Button Left After the new week program begins the system automatically switches to auto mode turning the manual mode off Figure 8 Manual mode parameters setting Figure 9 Manual mode parameters setting All ...

Page 8: ...User s Guide for CTS6000 Control panel Version 1 00 Subject to alteration without notice NILAN A S Page 8 of 11 Figure 10 Java GUI manual mode in PI Diagram All manuals and user guides at all guides com ...

Page 9: ... 23 7 C ANALOG1 100 ANALOG2 100 ANALOG3 000 ANALOG4 000 ANALOG5 000 ANALOG6 100 MONDAY PROGRAMME 1 2 PROGRAM POINT AKTIVE TIME 17 00 VENTILATION NORMALE SET POINT 20 0 COPY TO NEXT NO Week programme Date Time Language Unit Information Min Sommer Regulation Change Present Language Change Network IP Min Winter Netmask Max Sommer Winter Week Programme Restart Unit LA SORTIE SET CHANGE Date Time Statu...

Page 10: ...hour however Condenser high pressure ID 8 11 Level 4 Upper limit 2 for cooling circuit pressure set under Pressure limits has been exceeded The alarm can be activated by insufficient air flow through the unit This may be caused by blocked filters loose V belts or dampers which have not opened Reset alarm If the alarm repeatedly occurs for no apparent reason call service Evaporator low pressure 1 I...

Page 11: ...utes and reset the alarm Pressure pipe temperature T10 11 12 13 ID 50 51 52 53 Level 2 Pressure pipe temperature on compressor 1 2 3 4 has exceeded 125 C The controls stop the compressor and do not allow it to restart before the temperature has dropped below 50 C If the alarm repeatedly occurs call service VLT x has not responded to the 5 latest requests ID 111 Level 4 A communication error has oc...

Reviews: