7.2. Factory settings
ExtU address for door opening function
0
Relay switching time
approx. 3 sec.
Programming lock
OFF (= 0)
Switch relay contact upon receipt of the door opening protocol
ON (= 1)
Programming mode can only activated on power supply and control unit
ON (= 1)
Audio signal
ON (= 1)
Free protocols 1 to 4
00000000 (16 bit)
Master code
Serial number of the device
Master transponder code
00000000 (no master transponder)
RS485 activated
ON (= 1)
Bus connected
yes
7.3. Configuration options
Operation
Infrared remote control
Master transponder
Niko Configuration SW
Programming transponder
x
(up to 50)
x
(up to 10)
x
(up to 250)
Remove transponder
x
(remove separately)
number of memory location must be known
-
x
x
(remove all at once)
x
(remove all at once)
x
Set ExtU address
x
-
x
Set relay switch time
x
-
x
Load factory settings
x
-
x
Programming master transponder
x
-
x
Change master code
x
-
x
Activate programming lock
-
-
x
Free protocols 1 to 4
-
-
x
Programming with service unit 10-870 is not possible.
8. PROGRAMMING
8.1. Initial activation
For the initial activation you will need the infrared remote control.
As authorisation, enter the 6-digit serial number of the transponder reader.
Select a transponder as master transponder. Hold a transponder in front of the external unit and add labelling. Other transponders will be programmed using
the master transponder.
Terminate programming.
For safety reasons the preset master code must be changed when put into service!