8
GENERAL INFORMATION
POWERDRIVE MD2R Installation guide
4948 - 2017.11 / d
en
1.4 - Electrical characteristics
All work relating to installation, commissioning and maintenance must be carried out by experienced, qualified
personnel.
1.4.1 - General characteristics
Characteristic
Level
Power supply voltage
3-phase mains supply: 400 V -10% to 480 V +5% ("T" ratings) or
525 V -10% to 690 V +5% ("TH" ratings)
Phase voltage imbalance
< 2%
Input frequency
Rating «T» : 50Hz ou 60Hz + 5%
Rating «TH» : 50Hz + 5%
Maximum number of power-ups per hour (power)
20
Output frequency range
0 to 590 Hz
ROHS conformance
Conforming to standard 2002-95-EC
1.4.2 - Electrical characteristics
I
L
: Maximum line current allowed
. The user which uses the POWERDRIVE MD2R for controlling the reactive current of the mains needs check
that the global current of the line (active and reactive) does not exceed IL.
Ico
: Continuous output current.
Pout
: Output power.
Imax (60s)
: Maximum output current, available for 60 seconds every 600 seconds.
Heavy duty
: For heavy-duty constant torque machines (presses, grinders, hoisting, etc) and all applications where significant
inertia has to be accelerated quickly (centrifuges, translation of travelling cranes, etc).
Normal duty
: For normal-duty constant torque or centrifugal torque machines (fans, compressors, etc).
CAUTION: In its factory setting, the motor inverter operates with a switching frequency of 3 kHz.
POWERDRIVE MD2R xxxT
Inverter switching frequency = 3 kHz - Active rectifier in factory settings
Ambient temperature ≤ 40°C (35°C with an option IP54) - altitude ≤ 1000 m.
POWERDRIVE
MD2
rating
Maximum line
current
I
L
(A)
Heavy duty
Normal duty
Imax (60s)
(A)
Pout at 400V
(1) (kW)
Pout at 460V
(1) (HP)
Ico
(A)
Pout at 400V
(1) (kW)
Pout at 460V
(1) (HP)
Ico
(A)
60T
112
45
60
92
55
75
112
130
75T
142
55
75
118
75
100
142
165
100T
172
75
100
142
90
125
172
200
120T
200
90
125
170
110
150
200
240
150T
238
110
150
210
132
175
238
312
180T
310
132
175
260
160
200
310
365
220T
395
160
200
310
200
300
395
435
270T
465
200
300
375
250
350
465
530
340T
560
250
350
470
315
450
560
660
400T
610
315
450
535
355
500
610
760
470T
750
355
500
660
450
600
750
940
570T
815
400
600
715
500
650
815
1050
600T
1050
450
650
865
550
700
1050
1210
750T
1140
550
800
990
675
900
1140
1390
900T
1410
675
900
1225
800
1000
1410
1720
1100T
1530
800
1000
1345
900
1250
1530
1930
1400T
2110
900
1250
1850
1200
1500
2110
2590
1700T
2290
1200
1500
2015
1350
1700
2290
2890
(1) motor winding voltage.