Electric Power Generation 

Installation and maintenance 

5747 en - 2018.10 / a 

Dual plate D700 

 

 

 

1.4.  Safety devices and general safety instructions  

For the user's own safety, the dual plate D700 must be connected to approved earth terminals on the plate. The 
tools needed to make this connection are not included with the plate. 
 

 

Note: The 0Vs on the circuit boards of D700 AVRs are connected to earth 

 
It is essential to comply with the power connection diagrams recommended in this manual. 
 
The dual plate D700 contains devices which can, in the event of problems, control generator field weakening or 
overexcitation. This generator itself can become jammed for mechanical reasons. Finally, voltage fluctuations or 
power cuts may also cause the unit to stop. 
 
The  dual  plate  D700  which  is  the  subject  of  this  manual  is  designed  to  be  integrated  in  an  installation  or  an 
electrical  machine,  and  can  under  no  circumstances  be  considered  to  be  a  safety  device.  It  is  therefore  the 
responsibility  of  the  machine  manufacturer,  the  designer  of  the  installation  or  the  user  to  take  all  necessary 
precautions to ensure that the system complies with current applicable standards, especially safety standards, 
and to provide any devices required to ensure the safety of equipment and personnel (especially the prevention 
of direct or indirect contact when the plate is powered up). 
 
LEROY-SOMER declines all responsibility in the event of the above recommendations not being observed. 
 
The various interventions described in this manual are accompanied by recommendations or symbols to alert 
the  user  to  potential  risks  of  accidents.  It  is  vital  that  you  understand  and  take  note  of  the  different  safety 
instructions provided. 
 
This symbol warns of consequences which may arise from inappropriate use of the AVR or equipment, since 
electrical risks may lead to material or physical damage as well as constituting a fire hazard.  

 

 
This symbol alerts users to a safety instruction warning of electrical danger to personnel. 
 

 

1.4.1.  General information 

The  dual  plate  D700  may  contain  unprotected  live  parts,  as  well  as  hot  surfaces,  during  operation. 
Unjustified  removal  of  protection  devices,  incorrect  use,  faulty  installation  or  inappropriate  operation  could 
represent a serious risk to personnel and equipment. 
For further information, consult the documentation. 
All  work  relating  to  transportation,  installation,  commissioning  and  maintenance  must  be  performed  by 
experienced,  qualified  personnel  (see  IEC  364,  CENELEC  HD  384  or  DIN  VDE  0100,  as  well  as  national 
specifications for installation and accident prevention). 
In  these  basic  safety  instructions,  qualified  personnel  means  persons  competent  to  install,  mount, 
commission and operate the product and possessing the relevant qualifications. 

 

 

Summary of Contents for Leroy-Somer D700

Page 1: ...Dual plate Installation and maintenance D700...

Page 2: ......

Page 3: ...of the cabinet housing the dual plate 10 2 2 Connection block 10 2 3 Consumption 13 2 4 Wiring precautions 13 3 Setup instructions 14 3 1 Stator voltage and current measurement 14 3 2 Configuration fi...

Page 4: ...s for 10 seconds maximum 1 This plate has been designed to be installed in a control and power switching cabinet These cabinets must provide the minimum conditions for protection and safety of electri...

Page 5: ...of the generator field circuit Two freewheel diode modules connected on the field circuit to ensure it never opens All the controls 9 configurable inputs hard wired to deliver the same information to...

Page 6: ...ge 50 400 VDC 110 max 2 minutes Consumption 3000 VA Field current Rated 0 25 A Short circuit max 50 A at 25 C Field winding resistance 4 Ohm Frequency measurement Range 30 400 Hz For the plate 3 auxil...

Page 7: ...Electric Power Generation Installation and maintenance 5747 en 2018 10 a Dual plate D700 7 Fixings 371 32 28 8 352 06 CG CG 750 750 119 5 725 725...

Page 8: ...ally the prevention of direct or indirect contact when the plate is powered up LEROY SOMER declines all responsibility in the event of the above recommendations not being observed The various interven...

Page 9: ...cation of the clearance between components during transportation and handling Avoid touching the electronic components and contact parts The dual plate D700 contains parts which are sensitive to elect...

Page 10: ...you with any additional information you may require This manual is to be given to the end user 1 4 8 Protection of the equipment Auxiliary power supplies for the AVRs and the control circuit which ar...

Page 11: ...1 XM 13 Phase NW2 L2 XM 15 Phase NW3 L3 XM 12 Phase NW1 L1 Mains voltage measurement AVR 2 XM 14 Phase NW2 L2 XM 16 Phase NW3 L3 XP 1 Power X1 Field power AVR 1 XP 3 Power X2 XP 5 Power Z1 XP 7 Power...

Page 12: ...nd AVR 1 and 2 XC 16 Plate 24VDC XC 17 DI6 input command AVR 1 and 2 XC 18 Plate 24VDC XC 19 DI7 input command AVR 1 and 2 XC 20 Plate 24VDC XC 21 DI8 input command AVR 1 and 2 XC 22 Plate 24VDC XC 23...

Page 13: ...cable length must never exceed 100 m To ensure compliance with standards IEC 61000 6 2 IEC 61000 6 4 and IEC 60255 26 shielded cables are essential in the case of a D700 installed outside the termina...

Page 14: ...nd to the technical and electrical data of the generator on which the plate is to be installed It is therefore important to pay particular attention to the following settings Generator power rated vol...

Page 15: ...is checked In both cases the drawing on the right is updated with the appearance of a second D700 On the Protections page the following faults are automatically activated Machine fault tab reactive p...

Page 16: ...activated if the AVR is active DO2 and DO10 are activated if the AVR is online 3 3 Checks prior to commissioning First it is necessary to check the wiring and general operation of the plate Step 1 Ins...

Page 17: ...t breakers are closed properly in the generator Check that the status of both AVRs is OFF 3 4 Aligning measurements Once these checks have been done make sure that the measurements on both AVRs give s...

Page 18: ...ry or secondary values of the main stator current transformers and or isolating transformers General machine configuration Step 5 Setting the PF With the same load check the PF measurement on the wait...

Page 19: ...the serial link The regulation context is then preserved in the event of switching and running in manual mode 4 3 4 Switching on a fault Several faults can cause switching from the active AVR to the o...

Page 20: ...a circuit which monitors the power transistors If there is a discrepancy between the transistor command and its action the active AVR switches to fault mode and the online AVR switches to active mode...

Page 21: ...ching does not occur that may then come from the sensing VT Note By default no action has been programmed for loss of sensing A significant bump may therefore occur on switching to the online AVR This...

Page 22: ...that may then come from a fault in the link to the exciter Note By default no action has been programmed for reactive reverse power A significant bump may therefore occur on switching to the online AV...

Page 23: ...is firmly fixed on the plate Step 5 Electrical connections Wire up the earth connection Wire up the connectors in strict compliance with the plate wiring diagram CAUTION Reversing the wiring can serio...

Page 24: ...eck the functions work AVR internal power supply fault Replace the AVR Restart the plate with the procedure in section 4 3 5 Control 24 VDC power supply fault Plate general fault Replace the 24 VDC po...

Page 25: ...is available under reference P5 198 0003 5 1 2 Wiring diagrams The wring diagram for the dual plate D700 is available under reference WD 198 0003 5 2 Preventive maintenance instructions Check that th...

Page 26: ...Electric Power Generation Installation and maintenance 5747 en 2018 10 a Dual plate D700 26...

Page 27: ...ient repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to operate in al...

Page 28: ...www leroy somer com epg 2018 10 a Linkedin com company Leroy Somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel 5747 en...

Reviews: