Electric Power Generation
Installation and maintenance
5747 en - 2018.10 / a
Dual plate D700
12
Plate
Terminals
Generator
D700
Connection
XS.5
Phase
-
230 VAC power supply - AVR 2 (plate power supply redundancy)
XS.6
Phase
-
230 VAC power supply - Control circuit (plate power supply redundancy)
XC.1
-
-
Maintenance mode – AVR 1
XC.2
-
-
Plate +24VDC
XC.3
-
-
Maintenance mode reset – AVR 1
XC.4
-
-
Maintenance mode – AVR 2
XC.5
-
-
24VDC for AVR 2 maintenance mode
XC.6
-
-
Maintenance mode reset – AVR 2
XC.7
-
-
DI1 input command – AVR 1 and 2
XC.8
-
-
Plate +24VDC
XC.9
-
-
DI2 input command – AVR 1 and 2
XC.10
-
-
Plate +24VDC
XC.11
-
-
DI3 input command – AVR 1 and 2
XC.12
-
-
Plate +24VDC
XC.13
-
-
DI4 input command – AVR 1 and 2
XC.14
-
-
Plate +24VDC
XC.15
-
-
DI5 input command – AVR 1 and 2
XC.16
-
-
Plate +24VDC
XC.17
-
-
DI6 input command – AVR 1 and 2
XC.18
-
-
Plate +24VDC
XC.19
-
-
DI7 input command – AVR 1 and 2
XC.20
-
-
Plate +24VDC
XC.21
-
-
DI8 input command – AVR 1 and 2
XC.22
-
-
Plate +24VDC
XC.23
-
-
DI9 input command – AVR 1 and 2
XC.24
-
-
Plate +24VDC
XO1.1
-
DO11.1
Relay output – AVR 1
XO1.2
-
DO11.2
Relay output – AVR 1
XO1.3
-
DO12.1
Relay output – AVR 1
XO1.4
-
DO12.2
Relay output – AVR 1
XO2.1
-
DO11.1
Relay output – AVR 2
XO2.2
-
DO11.2
Relay output – AVR 2
XO2.3
-
DO12.1
Relay output – AVR 2
XO2.4
-
DO12.2
Relay output – AVR 2
Note: Unless requested by the customer, our plate contains connection shunts on the XM terminal block
so as to only have a single source for the generator voltage measurement, generator current, mains
voltage measurement and field excitation power signals. If there are separate sources, remove the
corresponding shunts. Please refer to the full diagram of plate reference WD 198 0003 for more details.