![Nidec D3-0023-B User Manual Download Page 58](http://html1.mh-extra.com/html/nidec/d3-0023-b/d3-0023-b_user-manual_1687787058.webp)
58
Digistart D3: User Guide
Issue: G
8.5 Quick setup details
To access the Quick Setup Menu, press the
M
button and select Quick Setup Menu.
The Quick Setup Menu makes it easy to configure the Digistart D3 for common applications. The Digistart D3 selects
the parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit
your exact requirements.
Always set Pr 1A
Motor Full Load Current
to match the motor's nameplate full load current. The suggested value is
the starter's minimum full load current.
Application
Parameter
Pr Number
Suggested value
Pump Centrifugal
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
1A
2A
2E
2D
2H
2K
2I
Model dependent
Adaptive Control
Early Acceleration
10 seconds
Adaptive Control
Late Deceleration
15 seconds
Pump Submersible
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
1A
2A
2E
2D
2H
2K
2I
Model dependent
Adaptive Control
Early Acceleration
5 seconds
Adaptive Control
Late Deceleration
5 seconds
Fan Damped
Motor Full Load Current
Start Mode
Current Limit
1A
2A
2B
Model dependent
Constant Current
350%
Fan Undamped
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Excess Start Time
Locked Rotor Time
1A
2A
2E
2D
5A
1C
Model dependent
Adaptive Control
Constant Acceleration
20 seconds
30 seconds
20 seconds
Compressor Screw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
1A
2A
2D
2B
Model dependent
Constant Current
5 seconds
400%
Compressor Recip
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
1A
2A
2D
2B
Model dependent
Constant Current
5 seconds
450%
Conveyor
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
1A
2A
2D
2B
2H
2K
2I
Model dependent
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
10 seconds
Crusher Rotary
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
1A
2A
2D
2B
5A
1C
Model dependent
Constant Current
10 seconds
400%
30 seconds
20 seconds