Digistart D3: User Guide
Issue: G
08605.
A
10. Unscrew and remove the magnetic bypass plates
(models D3-0620-N to D3-1600-N only).
11. Remove the current transformer assembly (three
screws).
12. Identify which busbars are to be moved. Remove the
bolts holding these busbars in place then slide the
busbars out through the bottom of the starter (four
bolts per busbar).
08606.
A
13. Slide the busbars in through the top of the starter. For
input busbars, the short curved end should be outside
the starter. For output busbars, the unthreaded hole
should be outside the starter.
14. Replace the dome washers with the flat face towards
the busbar, then tighten the bolts holding the busbars
in place to 20 Nm.
15. Place the current transformer assembly over the input
busbars and screw the assembly to the body of the
starter (see note).
16. Run all wiring to the side of the starter and secure with
cable ties.
NOTE
If moving the input busbars, the current transformers (CTs) must also be reconfigured.
1. Label the CTs L1, L2 and L3 (L1 is leftmost when looking from the front of the starter). Remove the
cable ties and unscrew the CTs from the bracket.
2. Move the CT bracket to the top of the starter. Position the CTs for the correct phases, then screw the
CTs to the bracket. For models D3-0360-N ~ D3-0930-N, the CTs must be placed on an angle (the left
hand legs of each CT will be on the top row of holes and the right hand legs will be on the bottom
tabs).