Digistart D3: User Guide
Issue: G
4.2 Control connections
08
34
7.
A
5
4
3
2
1
RLC3
COM3
COM1
RLO1
+24V
0V
RLO2
COM2
RLO3
AO1
0V
COM4
RLC4
RLO4
TH2
TH1
DI2
+24V
DI3
+24V
DI4
+24V
+24V
+24V
DI5
PT4
PT5
PT3
CSR
CSL
CSH
DI1
+10%
-15%
+10%
-15%
A
PT4
PT5
PT3
C
PT4
PT5
PT3
BB
E
7
6
220-440 VAC
110-210 VAC
1
Control voltage
DI1, +24V
Start
2
Remote control inputs
DI2, +24V
Stop
3
Motor thermistor input
DI3, +24V
Reset
4A
RTD/PT100 input - 2-wire
DI4, +24V
Programmable input A
4B
RTD/PT100 input - 3-wire
DI5, +24V
Programmable input B
4C
RTD/PT100 input - 4-wire
COM1, RLO1
Relay output A
5
24 VDC output
COM2, RLO2
Run relay output
6
Relay outputs
COM3, RLC3, RLO3 Relay output B
7
Analog output
COM4, RLC4, RLO4 Relay output C
The Digistart D3 can be disabled via the control inputs. An open circuit across DI4, +24V will disable the starter. The
Digistart D3 will not respond to start commands. If running, the soft starter will allow the motor to coast to stop,
ignoring the soft stop mode set in Pr 2H.
To use the starter disable function, set Pr 3A to 'Starter Disable' (this is the default setting).
If the Starter Disable function is not required, change the setting of Pr 3A or connect a link across DI4, +24V.
For keypad control, the soft starter requires:
•
control supply connections (terminals CSH, CSL, CSR depending on the control voltage)
•
programmable input A (DI4, +24V) must be closed or Pr 3A
Input A Function
must be changed from Starter
Disable