![Nidec D3-0023-B User Manual Download Page 12](http://html1.mh-extra.com/html/nidec/d3-0023-b/d3-0023-b_user-manual_1687787012.webp)
12
Digistart D3: User Guide
Issue: G
Inside delta connection
Internally bypassed
models
Light
300%, 10 seconds
50 ºC <1000 metres
Standard
350%, 30 seconds
50 ºC <1000 metres
Heavy
450%, 30 seconds
50 ºC <1000 metres
D3-0023-B
34 A
31 A
24 A
D3-0043-B
64 A
58 A
43 A
D3-0050-B
75 A
69 A
52 A
D3-0053-B
79 A
79 A
67 A
D3-0076-B
114 A
97 A
69 A
D3-0097-B
145 A
118 A
87 A
D3-0100-B
150 A
126 A
97 A
D3-0105-B
157 A
157 A
118 A
D3-0145-B
217 A
186 A
135 A
D3-0170-B
255 A
211 A
165 A
D3-0200-B
300 A
238 A
202 A
D3-0220-B
330 A
270 A
234 A
D3-0255-B
382 A
307 A
270 A
D3-0350-B
540 A
453 A
360 A
D3-0425-B
637 A
540 A
453 A
D3-0500-B
772 A
576 A
486 A
D3-0580-B
885 A
639 A
540 A
D3-0700-B
1050 A
772 A
646 A
D3-0820-B
1230 A
907 A
763 A
D3-0920-B
1380 A
1009 A
885 A
D3-1000-B
1500 A
1174 A
1080 A
Non-bypassed models
D3-0255-N
363 A
330 A
240 A
D3-0360-N
540 A
453 A
363 A
D3-0380-N
570 A
511 A
408 A
D3-0430-N
645 A
540 A
453 A
D3-0620-N
930 A
739 A
591 A
D3-0650-N
975 A
772 A
621 A
D3-0790-N
1185 A
991 A
790 A
D3-0930-N
1395 A
1126 A
895 A
D3-1200-N
1800 A
1722 A
1398 A
D3-1410-N
2115 A
1800 A
1468 A
D3-1600-N
2400 A
2166 A
1771 A