![Nidec D3-0023-B User Manual Download Page 34](http://html1.mh-extra.com/html/nidec/d3-0023-b/d3-0023-b_user-manual_1687787034.webp)
34
Digistart D3: User Guide
Issue: G
Ferraz/Mersen fuses - HSJ
Model
SCR I
2
T
(A
2
S)
Supply Voltage
(< 440 Vac)
Supply Voltage
(< 575 Vac)
Supply Voltage
(< 690 Vac)
D3-0023-B
1150
HSJ40**
HSJ40**
D3-0043-B
8000
HSJ80**
HSJ80**
D3-0050-B
10500
HSJ90**
HSJ90**
D3-0053-B
15000
HSJ110**
HSJ110**
D3-0076-B
15000
HSJ125**
HSJ125**
D3-0097-B
51200
HSJ175
HSJ175**
D3-0100-B
80000
HSJ175
HSJ175
D3-0105-B
125000
HSJ225
HSJ225
D3-0145-B
125000
HSJ250
HSJ250**
D3-0170-B
320000
HSJ300
HSJ300
D3-0200-B
320000
HSJ350
HSJ350
D3-0220-B
320000
HSJ400**
HSJ400**
D3-0255-B
320000
HSJ450*
HSJ450**
D3-0350-B
202000
HSJ500**
D3-0425-B
320000
Not suitable
D3-0500-B
320000
D3-0580-B
781000
D3-0700-B
781000
Not suitable
Not suitable
D3-0820-B
1200000
D3-0920-B
2530000
D3-1000-B
2530000
D3-0255-N
320000
HSJ450**
HSJ450**
D3-0360-N
320000
D3-0380-N
320000
D3-0430-N
320000
D3-0620-N
1200000
D3-0650-N
1200000
D3-0790-N
2530000
Not suitable
Not suitable
D3-0930-N
4500000
D3-1200-N
4500000
D3-1410-N
6480000
D3-1600-N
12500000
* Two parallel connected fuses required per phase.
** Two series connected fuses required per phase.