background image

12

 – English

EN

01.

 

Set dip switches 1-2-

3-4 to ON = the red 

and green LEDs start 

flashing quickly

ON

OFF

02.

 

Press and hold the 

STOP button for 3 sec. 

until the green and red 

LEDs remain lit

3”

ON

OFF

03.

 

Release the STOP 

button

04.

 

At this point the control 

unit performs a RESET 

= the red and green 

LEDs start flashing 

quickly

ON

OFF

RESET

05.

 

Set dip switches 1-2-3-

4 to OFF

ON

OFF

3.9 - Recognition of the safety devices and the Opening and 

Closing positions

After performing the initial startup (paragraph 3.7) and be

-

fore setting the door Opening and Closing positions, you 
must have the control unit run the recognition phase of 

the connected safety devices on the “STOP Safety Edge” 

input.

CAUTION!  -  During  the  recognition  phase,  at  least 

one safety device must be connected to the control 

unit.

OPEN

CLOSE

STOP

OPEN

STOP

CLOSE

01.

Set dip switch 1 to ON =

- Green LED begins to flash 

rapidly

- Red LED is OFF

ON

OFF

02.

Press and hold the STOP button 

until the red LED comes on and 

remains lit (after about 3 sec.)

3”

x 3

ON

OFF

03.

Release the STOP button

This  procedure  must  be  repeated  if  a  modification  is  made  to  the 

devices connected to the “STOP Safety Edge” terminal (for example, 

after connecting a new device to the control unit). 

After performing the recognition of the safety devices on the automated sys-

tem, the control unit must recognise the door Opening and Closing positions.

CAUTION! - The recognition procedure of the safety devices and the 

door Opening and Closing positions must be done consecutively, 

without interruption. You can not perform the recognition of the safety 

devices at one time and the recognition of the positions at another 

time.

CAUTION!  -  Procedure  for  motors  with  electronic  limit  switch:  after 

running the recognition procedure of the Opening and Closing posi-

tions, you need to get the control unit to perform the auto-recognition 

procedure of the memorised positions (5 cycles of complete manoeu-

vres with the door stopping in the Closing position). While performing 

these manoeuvres, the door gradually moves closer to the previously-

memorised positions until it reaches the programmed positions.

You need to follow different procedures according to the different types 

of motor:

- Motor with electronic limit switch (encoder), see paragraph 3.9.1;

- Motor with mechanical limit switch, see paragraph 3.9.2.

3.9.1 - Recognition of the Opening and Closing positions with elec-

tronic limit switch (encoder)

You can program 3 positions, as follows:

Position

Meaning

Opening

Maximum required opening position. When the door 

reaches this position it stops.

Partial Opening

Partial opening position. This is the position at which 
the door stops after receiving a partial opening com-
mand.

Closing

Maximum closing position. When the door reaches this 

position it stops.

If the door is in the closed position, you need to position it manually at about 

50  cm  above  the  ground,  using  the  emergency  manoeuvre  system  (see  the 

instruction manual for the motor). This is to avoid the supporting cables coming 

out of their housings, when rotating in reverse (sectional doors), or the exces

-

sive rolling up of the shutter (rolling shutters).

CAUTION! 

- If the direction of rotation does not correspond to the direction set 

(Open button = opening direction), you need to disconnect the mains 

power supply and invert the “V” and “W” connections (phase inversion) 

in the motor connector (Fig. 15). 

- If the door stops during movement and the (red) L1 WARNING LED 

with  diagnostics  flashes  3  times-pause-3  times,  press  the  red  STOP 

button and set the “Direction of rotation inverted” function; refer to  

Table 3.

V

W

U

L1

L2

L3

3 L

2 L

1 L

U

V

W

3 L

2 L

1 L

U

V

W

BRAKE

BOOST

15

To perform the procedure, proceed as follows:

01.

Dip switch 1 is already in the ON 

position, following the safety rec-

ognition procedure

ON

OFF

02.

Press the “Open” button to move 
the door to its maximum open po

-

sition

Caution!

- If the direction of rotation does not correspond to the set direction 

(Open button = opening direction), disconnect the mains power sup

-

ply and invert the “V” and “W” connections (phase inversion) in the 

motor connector (

Fig. 15

).

- If the door stops during movement and the (red) L1 WARNING LED 

with diagnostics flashes 3 times-pause-3 times, press the red STOP 
button to cancel the signal then set the “Direction of rotation inverted” 
function through dip switch 2; refer to 

Tab. 3

.

03.

Press and hold the STOP button 

for 3 sec. until the red LED flashes 
1 time

3”

x 1

ON

OFF

04.

Press the “Close” button to move 
the  door  to  its  maximum  closed 

position

Summary of Contents for D-Pro Action Series

Page 1: ...nstallazione e l uso FR Instructions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und...

Page 2: ......

Page 3: ...product as described in this instruction manual and for certain types of use e g excluding use solely for vehicles may cause the product to fall within the scope of Regulation No 305 2011 and its har...

Page 4: ...it is accessible to the public the command button must not be available to them e g use only with a key switch 2 For Semi automatic operation through the use of an active sensitive edge for limiting t...

Page 5: ...und the product allows safe and easy access Check that all electrical cables to be used belong to the type listed in Table 1 Check that the automation has mechanical stops in both the opening and clos...

Page 6: ...eed as follows when installing the control unit 01 Open the control unit box unscrew the screws as shown in Fig 3 A Fig 3 B 02 Prepare the holes for routing the electrical cables for the accessories p...

Page 7: ...Cable for FLASHING LIGHT with aerial 2 x 1 mm2 for 230 V AC flashing light RG58 type shielded cable aerial 10 m D PHOTOCELL cable 4 x 0 5 mm2 10 m E KEY SWITCH cable 2 cables 2 x 0 25 mm2 10 m note 2...

Page 8: ...inputs 8 com 24 V DC common 9 open 10 close 11 photo ing1 ALT ALT terminal SAFE only for motors with mechani cal limit switches leave uncon nected with motors which have electronic limit switches LIMI...

Page 9: ...ing movement It is possible to connect contacts of the Normally Open type to this input ING1 photo 11 Normally Closed NC input for devices that control the movement of the automation If this input is...

Page 10: ...echanical limit switch Fig 11A Three phase motor with electronic limit switch Fig 12A Three phase motor with mechanical limit switch and brake Fig 11B Three phase motor with electronic limit switch an...

Page 11: ...E 2 SMXI SMXIS Receiver in Mode 1 or 2 output description Output No 1 Step by Step Output No 2 Partial open factory setting it opens to halfway this may be changed during the position acquisition phas...

Page 12: ...ent procedures according to the different types of motor Motor with electronic limit switch encoder see paragraph 3 9 1 Motor with mechanical limit switch see paragraph 3 9 2 3 9 1 Recognition of the...

Page 13: ...n 03 a Set the limit switch cam 1 E green Fig 16 to operate the limit switch b Tighten the locking screw A Fig 16 c For precision adjustment use screw B Fig 16 04 Press the Close button to move the do...

Page 14: ...switch etc test the Opening Closing and Stopping of the door ensuring that the movement of the door leaves corresponds to specifications Test several times to assess the movement of the door and chec...

Page 15: ...s for a few seconds then try sending a command again if the problem persists there may be a serious fault on the circuit board or on the connections of the motor Carry out checks and replace parts if...

Page 16: ...no manoeuvre takes place and the flashing light is OFF check that the command is actually received if the command reaches the SS input the OK LED flashes twice to indicate that the command has been r...

Page 17: ...erminal and gnd STOP 8K2 OSE terminal see Fig 7 STOP SAFETY EDGE Input For contacts that are normally closed normally open or of the 8 2k constant resistance type or the OSE optical type in auto recog...

Page 18: ...harmonised standards EN 61000 6 2 2005 EN 61000 6 4 2007 A1 2011 In addition the product conforms to the following directive in accordance with the provisions applicable to partly completed machinery...

Reviews: