45
Place the stove on a floor-plate and check that the distances
between the stove and walls/ceiling are at least as great as
specified in the diagrams below. For top flue connections
to a modular (steel) chimney, please refer to the relevant
manufacturer’s assembly instructions.
Observe the requirements for safe distances to combustible
materials that apply to the steel chimney.
Always allow a gap of at least 1.0 metre from the opening in
the stove door to any combustible part of the building or any
interior fittings.
Installation distances to walls and ceiling
385
Brännbar vägg
135
820
760
280
Brännbar vägg
100
600
890
300
50
700
675
Brandmur av tegel eller betong
230
Brandmur av tegel eller betong
50
300*
590*
600
90**
350
1490
2150
min.
2200
Förbränningsluftsslang
(tillbehör)
Brännbart tak
C 180
325
455
490
B
1
1105
70
D 520
1665
A 1190
B
2
1825
105**
2150
A = height from floor to top flue connection
B
1
= height from floor to rear flue connection (c/c)
B
2
=c/c height from floor to rear flue connection, high-level elbow-joint
C = distance from back to top flue (c/c)
D = height from floor to underside of stove door
*
To avoid the risk of discoloration on painted, non-combustible
walls, we recommend the same gap at the sides as for combustible
walls.
**Important! When using a
prefabricated floor-plate for the
Handöl 20 series, please refer to
details of dimensions on page 46.
GB
Combustible wall
Combustible wall
Combustible ceiling
Flexible tubing for combustion
air (accessory)
Fire-retardant wall of
brick or concrete
Fire-retardant wall of
brick or concrete