Docking
FIGHTER 2010
For the Installer
8
FIGHTER 2010 can be installed in several different
ways. The safety equipment must be installed in
accordance with current regulations for all docking
options. See
www.nibe.se/vvs
for more docking
options.
When docking with FIGHTER 2010, a total water vol-
ume, incl. boiler, radiators, pipes, etc. of at least 15–20
litres boiler water per kW output on the heat pump is
recommended.
General
FIGHTER 2010 docked to the oil-fired/pellet boiler together with
SMO 10 and water heater (floating condensing)
VXV1
PG
SMO 10
HR
HR
HR
HR
P
VP
FG1
CP1
RG1 RG2
SV1
SV2
CP2
FG2
VVC
VVG
LP1
UG
RG
FG AV
SÄV
TV
RV
SF
SÄV
SMO 10 controls FIGHTER 2010, oil-fired boiler, circu-
lation pumps, shunts, etc. FIGHTER 2010 works with
floating condensing against the heating system and
prioritizes hot water charging via the reversing valve
(VXV1). FIGHTER 2010 works in stage 1 or stage 2
depending on the outdoor air temperature and the
heating requirement.
If FIGHTER 2010 cannot meet the heating require-
ment, the oil-fired boiler is started and additional heat-
ing is shunted in.
The above diagram is equipped with accessories.