NIBCO, Inc.
9
1516 Middlebury Street • Elkhart, IN 46516 USA • 888-446-4226
PC-10M Battery-powered Pressing Tool
Troubleshooting
Before You Begin
1. Make sure that the battery is charged. Recheck
the battery after several minutes to make sure the
battery is holding its charge.
2. Use a
nonflammable
contact cleaner or pencil
eraser to clean the electrical contacts on the battery
and pressing tool.
3. Reinstall the battery and check the tool again.
Problem
Probable Cause
Probable Remedy
Tool is inoperative.
Dirt, contaminants, etc., in ram area
Clean tool.
of tool.
Pressing tool battery contacts damaged.
Reform contacts.
Tool components worn or damaged.
Call NIBCO technical services for referral
to an authorized NIBCO service center.
Jaws stop during operation.
Oil level is low.
Call NIBCO technical services for referral
to an authorized NIBCO service center.
Air in hydraulic system.
Pull trigger and hold retract button
simultaneously. Hold for approximately
10 seconds.
Tool loses oil.
Damaged internal seal.
Call NIBCO technical services for referral
to an authorized NIBCO service center.