User Manual
Version 0.10
Use the arrows on the right to navigate to the loop that needs to be upgraded. By pressing the
Configure
button the loop configuration page will open.
If the USB is correctly identified by NURIA with the correct file in it, the button
Update Firmware
will
become active. Press the button to proceed to the update.
5.14
Factory defaults
Menu
→
Panel
→
Factory resets
If there is the need to clear data from the panels memory, in this menu it is possible to do so partially.
The list bellow shows which portions of data it is possible to reset:
•
Devices
- removes all devices from the system;
•
Zones
- sets all zone settings to factory defaults, devices will still maintain its associated zone;
•
Loops
- sets loops to default: Enable loop 1, disable the remaining loops;
•
Events
- removes all events, event inputs and event outputs;
•
Logs
- clear all the logs;
•
Network panels
- removes all stored network panels;
•
All data
- resets all data to factory default.
5.15
Earth leakage detection
Menu
→
Panel
→
Power
To inhibit errors coming from earth leakages, it is possible to disable their detection. When disabled the
panel will not generate any faults related to bad earth connections.
Warning
: Disabling earth leakage detections makes the panel non compliant with the EN54 standard
6
Operation
6.1
Fire alarm condition
When the panel receives a signal from a device which is interpreted as a fire signal, the panel enter in
the fire alarm condition and the fire alarm window (figure 9) opens on the top of the screen. When in this
condition, this window will open every 30 secs since the last user interaction with the panel.
6.1.1
Sounder delay
If a sounder delay is configured, the sounders will only be activated after the configured delay, this
condition is indicated by the
Delay active
visual indicator. When entering in the fire alarm condition, this
LED will start blinking. If the user is in access level 3, the
Add delay (30s)
will allow the operator to add 30
second delay up to a maximum of 10 minutes since the first alarm signal has been received by the panel.
6.2
System fault
6.2.1
Memory fault
In case of a damaged memory, the system will light the
System fault
indicator and will indicate which
zone of the memory is affected.
21
21 / 26