User Manual
Version 0.10
5.7
Global device configurations
Menu
→
Field
→
Global device configuration
This option can be use to globally change the parameters of some devices listed in table 9
Device type
Parameter
Detectors
Sensitivity
Sounders
Tone
Volume
Table 9:
Available parameter configuration.
5.8
Set date and time
Menu
→
Panel
→
Date and time
In order to correctly save the logs in the system the date and time must be correct. Navigate to this
menu and follow the instructions to change this settings.
5.9
Panel network
Menu
→
Panel
→
LAN connection
If there are multiple panels connected in a network using the Ethernet interface, this configuration is
required in order for it to work correctly.
5.9.1
IP address
To allow the communication between panels, each panel has to be assigned with an IP address, which
allows for it to be identified in a network. NURIA has the ability to configure its IP using the
or manually trough a
fixed IP
. To switch between configuration, just press the button
LAN Connection
or
Fixed IP
and edit the configuration accordingly. The
Link Status
will show if the panel is correctly
connected to the network by changing its value from
Offline
to
Has IP Address
.
5.10
Day/Night
Menu
→
Panel
→
Day / Night
This menu allows the user to configure and schedule the day and night times. This configuration is
relevant when sounder delay is active or for zones that are configured to behave differently during the day
or night, otherwise this configuration will have no impact in the system normal working mode.
There are three configurations available using the buttons in the bottom:
•
Night
- sets the panel in night mode, cancelling all configured sounder delays;
•
Day
- sets the panel in day mode, enabling all the configured sounder delays;
1
Dynamic Host Configuration Protocol - basically, the IP is given by the server.
19